Fault locator (FLOC)
&KDSWHU
0RQLWRULQJ
)DXOWORFDWRU)/2&
$SSOLFDWLRQ
The main objective of line protection and monitoring terminals is fast, selective and re-
liable operation for faults on a protected line section. Besides this, information on dis-
tance to fault is very important for those involved in operation and maintenance.
Reliable information on the fault location greatly decreases the downtime of the pro-
tected lines and increases the total availability of a power system.
The distance to the fault, which is calculated with a high accuracy, is stored for the last
ten recorded disturbances. This information can be read on the HMI or transferred via
serial communication within the Station Monitoring System (SMS) or Station Control
System (SCS).
The distance to fault can be recalculated for the latest 10 disturbances by using the mea-
suring algorithm for different fault loops or for changed system parameters.
)XQFWLRQDOLW\
'LVWDQFHWRIDXOWORFDWRU
The distance-to-fault locator (FLOC-) in the REx 5xx terminals is an essential comple-
ment to different line protection functions, since it measures and indicates the distance
to the fault with great accuracy. Thus, the fault can be quickly located for repairs.
The calculation algorithm considers the effect of load currents, double-end infeed and
additional fault resistance.
The function indicates the distance to the fault as a percentage of the line length, in ki-
lometers or miles as selected on the HMI.
The accuracy of measurement depends somewhat on the accuracy of the system param-
eters as entered into REx 5xx (for example source impedances at both ends of the pro-
tected line). If some parameters have actually changed in a significant manner relative
to the set values, new values can be entered locally or remotely and a recalculation of
the distance to the fault can be ordered. In this way, a more accurate location of the fault
can be achieved.
Any start of the disturbance reporting unit also starts the operation of the FLOC- func-
tion. The distance to the fault automatically appears on the local HMI, if the fault is also
detected by the phase selection elements within the terminal. The currents and voltages
before and during the fault are available via SCS/SMS. The terminal saves, in any other
Содержание REO 517
Страница 10: ... RQWHQWV ...
Страница 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Страница 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Страница 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Страница 100: ...90 Time delayed phase and residual overcurrent protection TOC1 KDSWHU XUUHQW Equation 36 Iset IsSEC I1b 100 ...
Страница 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Страница 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Страница 171: ...161 About this chapter KDSWHU RQWURO KDSWHU RQWURO ERXW WKLV FKDSWHU This chapter describes the control functions ...
Страница 293: ...283 About this chapter KDSWHU RJLF KDSWHU RJLF ERXW WKLV FKDSWHU This chapter describes the logic functions ...
Страница 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Страница 379: ...369 About this chapter KDSWHU 0HWHULQJ KDSWHU 0HWHULQJ ERXW WKLV FKDSWHU This chapter describes the metering functions ...
Страница 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Страница 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Страница 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...