![ABB REO 517 Скачать руководство пользователя страница 323](http://html.mh-extra.com/html/abb/reo-517/reo-517_applications-manual_5350323.webp)
313
Disturbance report (DRP)
&KDSWHU
0RQLWRULQJ
•
Analog-signal trigger (over/under function)
0DQXDOWULJJHU
A disturbance report can be manually triggered from the local HMI, a front-connected
PC, or SMS. When the trigger is activated, the manual trigger signal is generated. This
feature is especially useful for testing. Refer to Operators manual for procedure.
%LQDU\WULJJHU
Any binary signal state (logic one or a logic zero) can be selected to generate a trigger.
The binary signal must remain in a steady state for at least 15 ms to be valid.
When a binary signal is selected to generate a trigger from a logic zero, the selected sig-
nal will not be listed in the indications list of the disturbance report.
$QDORJWULJJHU
All analog signals are available for trigger purposes, no matter if they are recorded in
the disturbance recorder or not. But the disturbance recorder function must be installed
in the terminal.
5HWULJJHU
Under certain circumstances the fault condition may reoccur during the postfault re-
cording, for instance by automatic reclosing to a still faulty network. In order to capture
the new fault it is possible to allow retriggering during the PostFault recording.
&DOFXODWLRQV
The parameters for the disturbance report function are set via the local HMI or PST (Pa-
rameter Setting Tool). Refer to the Technical reference manual for setting parameters
and path in local HMI.
The settings include:
2SHUDWLRQ
Disturbance Report (On/Off)
5H7ULJ
Re-trigger during post-fault state (On/Off)
6HTXHQFH1R
Sequence number (0-255) (normally not necessary to set)
5HFRUGLQJ7LPHV
Recording times for the Disturbance Report and the event/indication
logging, including pre-fault time, post-fault time, and limit time for the
entire disturbance
Содержание REO 517
Страница 10: ... RQWHQWV ...
Страница 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Страница 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Страница 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Страница 100: ...90 Time delayed phase and residual overcurrent protection TOC1 KDSWHU XUUHQW Equation 36 Iset IsSEC I1b 100 ...
Страница 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Страница 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Страница 171: ...161 About this chapter KDSWHU RQWURO KDSWHU RQWURO ERXW WKLV FKDSWHU This chapter describes the control functions ...
Страница 293: ...283 About this chapter KDSWHU RJLF KDSWHU RJLF ERXW WKLV FKDSWHU This chapter describes the logic functions ...
Страница 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Страница 379: ...369 About this chapter KDSWHU 0HWHULQJ KDSWHU 0HWHULQJ ERXW WKLV FKDSWHU This chapter describes the metering functions ...
Страница 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Страница 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Страница 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...