2.5.8
LD0.SPCRGGIO1 Multipurpose binary outputs (1)
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse-
type outputs are triggered with the write value "1". Persistent-type outputs can be
written with both values "1" and "0". The setting mode "toggled" for local
operation corresponds to "persistent" for remote operation.
Table 151:
LD0.SPCRGGIO1 Multipurpose binary outputs (1)
0xA
CS
IEC 61850 name
SA name
Description
Values
LD0.SPCRGGIO1
2416
-
.SPCS01.ctlVal
Output 1 control
0/1=Off/On
2417
-
.SPCS02.ctlVal
Output 2 control
0/1=Off/On
2418
-
.SPCS03.ctlVal
Output 3 control
0/1=Off/On
2419
-
.SPCS04.ctlVal
Output 4 control
0/1=Off/On
2420
-
.SPCS05.ctlVal
Output 5 control
0/1=Off/On
2421
-
.SPCS06.ctlVal
Output 6 control
0/1=Off/On
2422
-
.SPCS07.ctlVal
Output 7 control
0/1=Off/On
2423
-
.SPCS08.ctlVal
Output 8 control
0/1=Off/On
2424
-
.SPCS09.ctlVal
Output 9 control
0/1=Off/On
2425
-
.SPCS10.ctlVal
Output 10 control
0/1=Off/On
2426
-
.SPCS11.ctlVal
Output 11 control
0/1=Off/On
2427
-
.SPCS12.ctlVal
Output 12 control
0/1=Off/On
2428
-
.SPCS13.ctlVal
Output 13 control
0/1=Off/On
2429
-
.SPCS14.ctlVal
Output 14 control
0/1=Off/On
2430
-
.SPCS15.ctlVal
Output 15 control
0/1=Off/On
2431
-
.SPCS16.ctlVal
Output 16 control
0/1=Off/On
Section 2
1MRS757822 B
Modbus data mappings
82
Recloser Protection and Control RER615