2.3.40
LD0.TRPPTRC1 Protection trip conditioning (1)
Table 43:
LD0.TRPPTRC1 Protection trip conditioning (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.TRPPTRC1
2740
171.04
.Op.general
-
Op.Input signal
1=Operate
2741
171.05
.mcd
2742
171.06
.Tr.general
-
Trip output signal
1=Trip
2743
171.07
.mcd
2.3.41
LD0.TRPPTRC2 Protection trip conditioning (2)
Table 44:
LD0.TRPPTRC2 Protection trip conditioning (2)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.TRPPTRC2
2744
171.08
.Op.general
-
Op.Input signal
1=Operate
2745
171.09
.mcd
2746
171.10
.Tr.general
-
Trip output signal
1=Trip
2747
171.11
.mcd
2.3.42
LD0.MAPGAPC1 Multipurpose analog protection function
(1)
Table 45:
LD0.MAPGAPC1 Multipurpose analog protection function (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.MAPGAPC1
3696
231.00
.Str.general
START
Stage start
1 = Start
3697
231.01
.mcd
3698
231.02
.Op.general
OPERATE
Stage operate
1 = Operate
3699
231.03
.mcd
Section 2
1MRS757822 B
Modbus data mappings
32
Recloser Protection and Control RER615
Point List Manual