BitA
RegA
IEC 61850 name
SA name
Description
Values
2851
178.03
.OpNumAlm.stVal
OPR_ALM
CB operations alarm
1=Alarm
2852
178.04
.OpNumLO.stVal
OPR_LO
CB operations lockout
1=Lockout
2853
178.05
.LonTmAlm.stVal
MON_ALM
CB inactive alarm
1=Alarm
2854
178.06
.PresAlm.stVal
PRES_ALM
Low pressure alarm
1=Alarm
2855
178.07
.PresLO.stVal
PRES_LO
Low pressure lockout
1=Lockout
2856
178.08
.APwrAlm.stVal
IPOW_ALM
Lyt alarm
1=Alarm
2857
178.09
.APwrLO.stVal
IPOW_LO
Lyt lockout
1=Lockout
2858
178.10
.CBLifAlm.stVal
CB_LIFE_ALM
CB lifetime alarm
1=Alarm
2.3.61
LD0.TCSSCBR1 Trip circuit supervision (1)
Table 64:
LD0.TCSSCBR1 Trip circuit supervision (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.TCSSCBR1
2780
173.12
.CirAlm.stVal
ALARM
Supervision alarm
1=Alarm
2781
173.13
.mcd
2.3.62
LD0.TCSSCBR2 Trip circuit supervision (2)
Table 65:
LD0.TCSSCBR2 Trip circuit supervision (2)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.TCSSCBR2
2782
173.14
.CirAlm.stVal
ALARM
Supervision alarm
1=Alarm
2783
173.15
.mcd
2.3.63
LD0.SEQRFUF1 Fuse failure protection (1)
Table 66:
LD0.SEQRFUF1 Fuse failure protection (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.SEQRFUF1
2996
187.04
.Str.general
FUSEF_U
Start
1=Start
2997
187.05
.mcd
2998
187.06
.Str3Ph.general
FUSEF_3PH
3-phase start
1=Start
2999
187.07
.mcd
1MRS757822 B
Section 2
Modbus data mappings
Recloser Protection and Control RER615
39
Point List Manual