![ABB Relion RER615 Скачать руководство пользователя страница 61](http://html.mh-extra.com/html/abb/relion-rer615/relion-rer615_modbus-point-list-manual_2828061.webp)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
128.13
Bit
< reserved >
0
128.14
Bit
< reserved >
0
128.15
Bit
< reserved >
0
2.4.4
SSR2 System status register (2) IED mode and state
Table 95:
SSR2 System status register (2) IED mode and state
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
129.00
Bit
Device test mode
1=Test mode
129.01
Bit
< reserved >
0
129.02
Bit
Remote/Local state
0/1=Rem/Loc
Active setting group
SG=1...6
129.03
Bit
- bit 0
129.04
Bit
- bit 1
129.05
Bit
- bit 2
129.06
Bit
IED timesynch failure
1=Failure
129.07
Bit
< reserved >
0
129.08
Bit
Last reset cause a
1=Cold start
129.09
Bit
Last reset cause b
1=Watchdog
129.10
Bit
Last reset cause c
1=Warm start
129.11
Bit
< reserved >
0
129.12
Bit
< reserved >
0
129.13
Bit
< reserved >
0
129.14
Bit
< reserved >
0
129.15
Bit
< reserved >
0
2.4.5
SSR3 System status register (3) data available 1 (client-
dependent)
Table 96:
SSR3 System status register (3) data available 1 (client-dependent)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
130.00
Bit
Unread event records available 1=Available
130.01
Bit
Unread fault records available
1=Available
130.02
Bit
< reserved >
0
130.03
Bit
< reserved >
0
130.04
Bit
Any momentary bit updated
1=Updated
130.05
Bit
Any mcd bit set
1=Set
130.06
Bit
Device restart bit
1=IED restart
130.07
Bit
< reserved >
0
Table continues on next page
1MRS757822 B
Section 2
Modbus data mappings
Recloser Protection and Control RER615
55
Point List Manual