![ABB Relion RER615 Скачать руководство пользователя страница 21](http://html.mh-extra.com/html/abb/relion-rer615/relion-rer615_modbus-point-list-manual_2828021.webp)
Section 2
Modbus data mappings
2.1
Overview
This document describes the Modbus data points and structures available in the
IED. The point lists describe a superset of all data available through the standard
configuration/s including the optional functionalities.
The majority of the Modbus data points are valid for all standard configurations.
Some data points are standard configuration-dependent or optional application-
dependent and thus not available in each IED. The unavailable, that means, unused,
data points always return value 0 when they are read. The configuration-dependent
and optional data do not overlap.
2.2
Supported functions in RER615
Table 2:
Supported functions
Function
IEC 61850
A
D
RE01
RE02
Protection
1)2)
Three-phase non-directional overcurrent protection, low stage
FPHLPTOC
(1)
3)
(1)
3)
Three-phase non-directional overcurrent protection, high stage
PHHPTOC
(1)
3)
(1)
3)
Three-phase non-directional overcurrent protection, instantaneous stage
PHIPTOC
1
1
Three-phase directional overcurrent protection, low stage
FDPHLPDOC
(2)
3)
(2)
3)
Three-phase directional overcurrent protection, high stage
DPHHPDOC
(1)
3)
(1)
3)
Non-directional earth-fault protection, low stage
FEFLPTOC
(1)
4)5)
(1)
4)5)
Non-directional earth-fault protection, high stage
EFHPTOC
(1)
4)5)
(1)
4)5)
Non-directional earth-fault protection, instantaneous stage
EFIPTOC
1
5)
1
5)
Directional earth-fault protection, low stage
FDEFLPDEF
(2)
5)6)7)
(2)
5)6)7)
Directional earth-fault protection, high stage
DEFHPDEF
(1)
5)6)7)
(1)
5)6)7)
Transient / intermittent earth-fault protection
INTRPTEF
(1)
5)6)7)
(1)
5)6)7)
Admittance based earth-fault protection
EFPADM
(3)
5)7)8)
(3)
5)7)8)
Wattmetric based earth-fault protection
WPWDE
(3)
5)7)8)
(3)
5)7)8)
Harmonics based earth-fault protection
HAEFPTOC
(1)
5)8)
(1)
5)8)
Negative-sequence overcurrent protection
NSPTOC
2
2
Phase discontinuity protection
PDNSPTOC
1
1
Residual overvoltage protection
ROVPTOV
(1)
7)
(2)
9)10)
Table continues on next page
1MRS757822 B
Section 2
Modbus data mappings
Recloser Protection and Control RER615
15
Point List Manual