2.3.69
LD0.VMMXU2 Phase voltage limit supervision (2)
Table 72:
LD0.VMMXU2 Phase voltage limit supervision (2)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.VMMXU2
3360
210.00
.HiAlm.stVal
HIGH_ALARM
High alarm
1=Alarm
3361
210.01
.mcd
3362
210.02
.HiWrn.stVal
HIGH_WARN
High warning
1=Warning
3363
210.03
.mcd
3364
210.04
.LoWrn.stVal
LOW_WARN
Low warning
1=Warning
3365
210.05
.mcd
3366
210.06
.LoAlm.stVal
LOW_ALARM
Low alarm
1=Alarm
3367
210.07
.mcd
2.3.70
LD0.MVGAPC1 Multipurpose binary inputs (1)
Table 73:
LD0.MVGAPC1 Multipurpose binary inputs (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.MVGAPC1
3536
221.00
.Q1.stVal
Input 1
0/1=Off/On
3537
221.01
.mcd
3538
221.02
.Q2.stVal
Input 2
0/1=Off/On
3539
221.03
.mcd
3540
221.04
.Q3.stVal
Input 3
0/1=Off/On
3541
221.05
.mcd
3542
221.06
.Q4.stVal
Input 4
0/1=Off/On
3543
221.07
.mcd
3544
221.08
.Q5.stVal
Input 5
0/1=Off/On
3545
221.09
.mcd
3546
221.10
.Q6.stVal
Input 6
0/1=Off/On
3547
221.11
.mcd
3548
221.12
.Q7.stVal
Input 7
0/1=Off/On
3549
221.13
.mcd
3550
221.14
.Q8.stVal
Input 8
0/1=Off/On
3551
221.15
.mcd
Section 2
1MRS757822 B
Modbus data mappings
42
Recloser Protection and Control RER615