![ABB Relion RER615 Скачать руководство пользователя страница 43](http://html.mh-extra.com/html/abb/relion-rer615/relion-rer615_modbus-point-list-manual_2828043.webp)
2.3.57
LD0.DARREC1 AR state (1)
Table 60:
LD0.DARREC1 AR state (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.DARREC1
2724
170.04
.AROn.stVal
AR_ON
AutoRecloser state
0/1=Off/On
2.3.58
LD0.DARREC1 Autorecloser (1)
Table 61:
LD0.DARREC1 Autorecloser (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.DARREC1
3040
190.00
.PrgRec.stVal
INPRO
AR in progess
1=In progress
3041
190.01
.mcd
3042
190.02
.PrgRec1.stVal
INPRO_1
1st shot in progess
1=In progress
3043
190.03
.mcd
3044
190.04
.PrgRec2.stVal
INPRO_2
2nd shot in progess
1=In progress
3045
190.05
.mcd
3046
190.06
.PrgRec3.stVal
INPRO_3
3rd shot in progess
1=In progress
3047
190.07
.mcd
3048
190.08
.PrgRec4.stVal
INPRO_4
4th shot in progess
1=In progress
3049
190.09
.mcd
3050
190.10
.PrgRec5.stVal
INPRO_5
5th shot in progess
1=In progress
3051
190.11
.mcd
3052
190.12
.SucRec.stVal
SUC_RECL
Successful AR
1=Success
3053
190.13
.mcd
3054
190.14
.UnsRec.stVal
UNSUC_RECL
Unsuccessful AR
1=Unsuccess
3055
190.15
.mcd
3056
191.00
< reserved >
3057
191.01
< reserved >
3058
191.02
< reserved >
3059
191.03
< reserved >
3060
191.04
.LO.stVal
LOCKED
Lockout status
1=Lockout
3061
191.05
.mcd
3062
191.06
.RdyRec.stVal
READY
Reclose ready
1=Ready
3063
191.07
.mcd
3064
191.08
.ActRec.stVal
ACTIVE
Reclose active
1=Active
3065
191.09
.mcd
3066
191.10
.PrgDsr.stVal
DISCR_INPRO
Discr.time in progress
1=In progress
3067
191.11
.mcd
Table continues on next page
1MRS757822 B
Section 2
Modbus data mappings
Recloser Protection and Control RER615
37
Point List Manual