2.3.13
LD0.DEFHPDEF1 Directional earth-fault protection, high
stage (1)
Table 16:
LD0.DEFHPDEF1 Directional earth-fault protection, high stage (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.DEFHPTOC1
2928
183.00
.Str.general
START
Stage start
1=Start
2929
183.01
.mcd
2930
183.02
.Op.general
OPERATE
Stage operate
1=Operate
2931
183.03
.mcd
2.3.14
LD0.INTRPTEF1 Intermittent earth fault protection (1)
Table 17:
LD0.INTRPTEF1 Intermittent earth fault protection (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.INTRPTEF1
3176
198.08
.Str.general
START
General Start
1=Start
3177
198.09
.mcd
3178
198.10
.Op.general
OPERATE
General Operate
2=Operate
3179
198.11
.mcd
2.3.15
LD0.EFPADM1 Admittance-based earth-fault protection (1)
Table 18:
LD0.EFPADM1 Admittance-based earth-fault protection (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.EFPADM1
2840
177.08
.Str.general
START
Stage start
1=Start
2841
177.09
.mcd
2842
177.10
.Op.general
OPERATE
Stage operate
1=Operate
2843
177.11
.mcd
2.3.16
LD0.EFPADM2 Admittance-based earth-fault protection (2)
Table 19:
LD0.EFPADM2 Admittance-based earth-fault protection (2)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.EFPADM2
2844
177.12
.Str.general
START
Stage start
1=Start
2845
177.13
.mcd
2846
177.14
.Op.general
OPERATE
Stage operate
1=Operate
2847
177.15
.mcd
1MRS757822 B
Section 2
Modbus data mappings
Recloser Protection and Control RER615
23