![ABB Relion RER615 Скачать руководство пользователя страница 82](http://html.mh-extra.com/html/abb/relion-rer615/relion-rer615_modbus-point-list-manual_2828082.webp)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
Record 10 data to read:
If selected
9351
u16
1
- Record sequence num
1...9999
9352
u16
1
- Unread records left
0...499
Timestamp of record
9353
u16
1
- Year, Month
Year/Month
9354
u16
1
- Day, Hour
Day/Hour
9355
u16
1
- Minute, Second
Min/Sec
9356
u16
1
- Millisecond
Millisecond
9357
u16
1
Event identification
1)
9358
u16
1
Data object ID1
1)
9359
u16
1
Data object ID2
1)
9360
u16
1
Event data value 1
1)
9361
u16
1
Event data value 2
1)
1) See the technical manual.
2.4.50
Fault record structure header
Table 141:
Fault record structure header
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
Selection write:
9401
u16
- Read selection
-99...3
Record data header:
9402
u16
- Record sequence num
0...65535
9403
u16
- Unread records left
0...99
Timestamp of record:
9404
u16
- Year, month
Year/Month
9405
u16
- Day, hour
Day/Hour
9406
u16
- Minute, second
Min/Sec
9407
u16
- Millisecond
Millisecond
9408
u16
- Timestamp quality
1)
LD0.FLTMSTA1
9409
u16
100
.StrDur.mag
- Start duration
0...100.00 [%]
9410
u16
1
.ActSG.stVal
- Active setting group
1...6
9411
u16
100
.FltDiskm.mag
- Fault distance
0...9999.99
[pu]
9412
u16
< reserved >
0
9413
u16
< reserved >
0
9414
u16
< reserved >
0
9415
u16
< reserved >
0
Table continues on next page
Section 2
1MRS757822 B
Modbus data mappings
76
Recloser Protection and Control RER615
Point List Manual