![ABB Relion RER615 Скачать руководство пользователя страница 65](http://html.mh-extra.com/html/abb/relion-rer615/relion-rer615_modbus-point-list-manual_2828065.webp)
2.4.12
LD0.PHQVVR1 Short duration voltage variations (1)
Table 103:
LD0.PHQVVR1 Short duration voltage variations (1)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.PH1QVVR1
Voltage swell:
2100
u32
1
.SwlInstCnt.stVal
INSTSWELLCNT
- Inst counter (high)
0…
2101
- (low word)
2147483647
2102
u32
1
.SwlMomCnt.stVal
MOMSWELLCNT
- Mom counter (high)
0…
2103
- (low word)
2147483647
2104
u32
1
.SwlTmpCnt.stVal
TEMPSWELLCNT
- Temp counter (high)
0…
2105
- (low word)
2147483647
2106
u32
1
.SwlMaxCnt.stVal
MAXDURSWELLC
NT
- Max duration.counter (high)
0…
2107
- (low word)
2147483647
Voltage dip:
2108
u32
1
.DipInstCnt.stVal
INSTDIPCNT
- Inst counter (high)
0…
2109
- (low word)
2147483647
2110
u32
1
.DipMomCnt.stVal
MOMDIPCNT
- Mom counter (high)
0…
2111
- (low word)
2147483647
2112
u32
1
.DipTmpCnt.stVal
TEMPDIPCNT
- Temp counter (high)
0…
2113
- (low word)
2147483647
2114
u32
1
.DipMaxCnt.stVal
MAXDURDIPCNT
- Max duration.counter (high)
0…
2115
- (low word)
2147483647
Voltage interrupts:
2116
u32
1
.IntrMomCnt.stVal
MOMINTCNT
- Mom counter (high)
0…
2117
- (low word)
2147483647
2118
u32
1
.IntrTmpCnt.stVal
TEMPINTCNT
- Temp counter (high)
0…
2119
- (low word)
2147483647
2120
u32
1
.IntrSstCnt.stVal
SUSTINTCNT
- Sustain counter (high)
0…
2121
- (low word)
2147483647
2122
u32
1
.IntrMaxCnt.stVal
MAXDURINTCNT
- Max duration.counter (high)
0…
2.4.13
LD0.DARREC1 Autorecloser values (1)
Table 104:
LD0.DARREC1 Autorecloser values (1)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.DARREC1
135
i16
1
.AutoRecSt.stVal
STATUS
AR state
-2...4
1)
136
u16
1
.ShotPntr.stVal
SHOT_PTR
AR shot pointer value
0...6
137
u16
1
.OpCntRs.stVal
COUNTER
AR operation counter
0...65535
1) See the technical manual.
1MRS757822 B
Section 2
Modbus data mappings
Recloser Protection and Control RER615
59