ALARM is red and green for OK. Colors can, however, be reconfigured with a
setting parameter.
OK
ALARM
RESET
LEDx
OK
ALARM
RESET
LEDx
Signal
Signal
GUID-775477F8-C2DE-4138-B2C0-6B7C2774D4D2 V1 EN
Figure 2:
Signal wired to either OK or Alarm input
Table 81:
LD0.LEDGGIO1 Indication LED states OFF/ColorX
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.LEDGGIO1
2768
173.00
.ISCSO1.stVal
-
LED 1 state
0/1=Off/Color
2769
173.01
.ISCSO2.stVal
-
LED 2 state
0/1=Off/Color
2770
173.02
.ISCSO3.stVal
-
LED 3 state
0/1=Off/Color
2771
173.03
.ISCSO4.stVal
-
LED 4 state
0/1=Off/Color
2772
173.04
.ISCSO5.stVal
-
LED 5 state
0/1=Off/Color
2773
173.05
.ISCSO6.stVal
-
LED 6 state
0/1=Off/Color
2774
173.06
.ISCSO7.stVal
-
LED 7 state
0/1=Off/Color
2775
173.07
.ISCSO8.stVal
-
LED 8 state
0/1=Off/Color
2776
173.08
.ISCSO9.stVal
-
LED 9 state
0/1=Off/Color
2777
173.09
.ISCSO10.stVal
-
LED 10 state
0/1=Off/Color
2778
173.10
.ISCSO11.stVal
-
LED 11 state
0/1=Off/Color
2779
173.11
<reserved>
0
2.3.79
LD0.LEDGGIO1 Indication LED states Color1/Color2
These LED indication points interpret the case when a signal is wired to both the
OK and ALARM inputs, but inverted to the other. This means that the LED toggles
between red and green colors. The default color for ALARM is red and green for
OK. Colors can, however, be reconfigured with a setting parameter.
Section 2
1MRS757822 B
Modbus data mappings
48
Recloser Protection and Control RER615
Point List Manual