2.4.17
LD0.MDSOPT1 Generic operation time supervision
Since the register size is 16 bits, the value saturates at 65535 hours (approximately
7.5 years). Alternatively, a 32-bit user-definable register can be made of this data to
cover the whole 300 000 hours (34 years) range. The value can also, for example,
be rescaled to show “total operation days” instead by changing the scale factor
from 1 to 1/24 = 0.0417.
Table 108:
LD0.MDSOPT1 Generic operation time supervision
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
2048
u16
1
.stVal
OPR_TIME
Operating hours
0…299999
[hours]
2.4.18
LD0.CMMXU1 Phase current measurements (1)
Table 109:
LD0.CMMXU1 Phase current measurements (1)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.CMMXU1
Phase current (1)
138
u16
1000
.A.phsA.instCVal.mag
I_INST_A
- phsA amplitude
0.00...40.0
[xIn]
139
u16
1000
.A.phsB.instCVal.mag
I_INST_B
- phsB amplitude
0.00...40.0
[xIn]
140
u16
1000
.A.phsC.instCVal.mag
I_INST_C
- phsC amplitude
0.00...40.0
[xIn]
2.4.19
LD0.CMSQI1 Sequence of current measurements (1)
Table 110:
LD0.CMSQI1 Sequence of current measurements (1)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.CMSQI1
Sequence of currents
143
u16
1000
.SeqA.c1.instCVal.mag
I1_INST
- positive amplitude
0.00...40.0
[xIn]
144
u16
1000
.SeqA.c2.instCVal.mag
I2_INST
- negative amplitude
0.00...40.0
[xIn]
145
u16
1000
.SeqA.c2.instCVal.mag
I3_INST
- zero amplitude
0.00...40.0
[xIn]
2.4.20
LD0.RESCMMXU1 Residual current measurement (1)
Table 111:
LD0.RESCMMXU1 Residual current measurement (1)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.RESCMMXU1
Residual current (1)
141
u16
1000
.A.res.instCVal.mag
I0_INST
- amplitude
0.00...40.0
[xIn]
1MRS757822 B
Section 2
Modbus data mappings
Recloser Protection and Control RER615
61
Point List Manual