2.3.46
LD0.MAPGAPC5 Multipurpose analog protection function
(5)
Table 49:
LD0.MAPGAPC5 Multipurpose analog protection function (5)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.MAPGAPC5
3712
232.00
.Str.general
START
Stage start
1 = Start
3713
232.01
.mcd
3714
232.02
.Op.general
OPERATE
Stage operate
1 = Operate
3715
232.03
.mcd
2.3.47
LD0.MAPGAPC6 Multipurpose analog protection function
(6)
Table 50:
LD0.MAPGAPC6 Multipurpose analog protection function (6)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.MAPGAPC6
3716
232.04
.Str.general
START
Stage start
1 = Start
3717
232.05
.mcd
3718
232.06
.Op.general
OPERATE
Stage operate
1 = Operate
3719
232.07
.mcd
2.3.48
LD0.CMHAI1 Current total demand distortion (1)
Table 51:
LD0.CMHAI1 Current total demand distortion (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.CMHAI1
3316
207.04
.Alm.stVal
ALARM
1=Alarm
3317
207.05
.mcd
2.3.49
LD0.VMHAI1 Voltage total demand distortion (1)
Table 52:
LD0.VMHAI1 Voltage total demand distortion (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.VMHAI1
3318
207.06
.Alm.stVal
ALARM
1=Alarm
3319
207.07
.mcd
Section 2
1MRS757822 B
Modbus data mappings
34
Recloser Protection and Control RER615
Point List Manual