2.3.17
LD0.EFPADM3 Admittance-based earth-fault protection (3)
Table 20:
LD0.EFPADM3 Admittance-based earth-fault protection (3)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.EFPADM3
2860
178.12
.Str.general
START
Stage start
1=Start
2861
178.13
.mcd
2862
178.14
.Op.general
OPERATE
Stage operate
1=Operate
2863
178.15
.mcd
2.3.18
LD0.WPWDE1 Wattmetric-based earth-fault protection (1)
Table 21:
LD0.WPWDE1 Wattmetric-based earth-fault protection (1)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.WPSDE1
3296
206.00
.Str.general
START
Stage start
1=Start
3297
206.01
.mcd
3298
206.02
.Op.general
OPERATE
Stage operate
1=Operate
3299
206.03
.mcd
2.3.19
LD0.WPWDE2 Wattmetric-based earth-fault protection (2)
Table 22:
LD0.WPWDE2 Wattmetric-based earth-fault protection (2)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.WPSDE2
3300
206.04
.Str.general
START
Stage start
1=Start
3301
206.05
.mcd
3302
206.06
.Op.general
OPERATE
Stage operate
1=Operate
3303
206.07
.mcd
2.3.20
LD0.WPWDE3 Wattmetric-based earth-fault protection (3)
Table 23:
LD0.WPWDE3 Wattmetric-based earth-fault protection (3)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.WPSDE3
3304
206.08
.Str.general
START
Stage start
1=Start
3305
206.09
.mcd
3306
206.10
.Op.general
OPERATE
Stage operate
1=Operate
3307
206.11
.mcd
Section 2
1MRS757822 B
Modbus data mappings
24
Recloser Protection and Control RER615
Point List Manual