2.3.87
LD0.XAGGIO130 Physical I/O states (AIM card XA130)
Table 90:
LD0.XAGGIO130 Physical I/O states (AIM card XA130)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.XAGGIO130
3280
205.00
.Ind1.stVal
XA130-Input 1 State
0/1=Off/On
3281
205.01
.mcd
3282
205.02
.Ind2.stVal
XA130-Input 2 State
0/1=Off/On
3283
205.03
.mcd
3284
205.04
.Ind3.stVal
XA130-Input 3 State
0/1=Off/On
3285
205.05
.mcd
3286
205.06
.Ind4.stVal
XA130-Input 4 State
0/1=Off/On
3287
205.07
.mcd
2.4
Registers
Table 91:
Explanations of columns in register tables
Column name
Description
RegA
Default 3X and 4X register address for the data.
Type
Type of the register. The alternatives are u16, u32 (unsigned 16 and 32 bits
integer) or i16, i32 (signed 16 and 32 bit integer).
Scale
Scale factor as default. Also, an adjustable offset value exists that is set to 0 by
default.
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description
Short description of the signal. See the technical manual for more information.
Also, if a register is writable, it is stated here.
Values
The value range of the original IEC 61850 value, that is, before scaling.
2.4.1
User definable registers [Alt.1], visible on 3x and 4x
Table 92:
User definable registers [Alt.1], visible on 3x and 4x
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
(0)
Reg
< not mappable- not visible >
1
Reg
User Register 1
2
Reg
User Register 2
3
:
:
Table continues on next page
1MRS757822 B
Section 2
Modbus data mappings
Recloser Protection and Control RER615
53