2.4.31
LD0.RESCMSTA1 Residual current demand value (1)
Table 122:
LD0.RESCMSTA1 Residual current demand value (1)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.RESCMSTA1
Demand value
1989
u16
1000
.AvAmps.mag
I_DMD_RES
- residual amplitude
0.00...40.0
[xIn]
Update time stamp
1)
1990
u16
-
- Year - month
1991
u16
-
- Day - hour
1992
u16
-
- Minute - second
1993
u16
-
- Milliseconds
1994
u16
-
- Time quality
1995
u16
1000
.MaxAmps.mag
Max demand Io
- Max Io demand
0.00...40.0
[xIn]
Update time stamp
1)
1996
u16
-
- Year - month
1997
u16
-
- Day - hour
1998
u16
-
- Minute - second
1999
u16
-
- Milliseconds
2000
u16
-
- Time quality
1) See the technical manual.
2.4.32
LD0.CMSTA1 Phase current demand values (1)
Table 123:
LD0.CMSTA1 Phase current demand values (1)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.CMSTA1
Demand value
2001
u16
1000
.AvAmpsA.mag
I_DMD_A
- phsA amplitude
0.00...40.0
[xIn]
2002
u16
1000
.AvAmpsB.mag
I_DMD_B
- phsB amplitude
0.00...40.0
[xIn]
2003
u16
1000
.AvAmpsC.mag
I_DMD_C
- phsC amplitude
0.00...40.0
[xIn]
Update time stamp
1)
2004
u16
-
- Year - month
2005
u16
-
- Day - hour
2006
u16
-
- Minute - second
2007
u16
-
- Milliseconds
2008
u16
-
- Time quality
Table continues on next page
Section 2
1MRS757822 B
Modbus data mappings
66
Recloser Protection and Control RER615
Point List Manual