SNMP Network Management
Functions
Object name
Read object
Write object
firmwareVersion
1.3.6.1.4.1.21939.9.1.1.2.0
Coded version of the
firmwareversion, shows as 4
bytes:
–Byte 0: Version Main
–Byte 1: Version Major
–Byte 2: Version Minor
–Byte 3: Version Flags
Example: Version 1.37.3 coded
as hex 01 25 03 00, decimal
19202816
subsystemVersion
1.3.6.1.4.1.21939.9.1.1.3.0
Coded version of the sub-sys-
tem if applicable
cpldVersion
1.3.6.1.4.1.21939.9.1.1.4.0
Coded version of the CPLD if
applicable
systemDescription
1.3.6.1.4.1.21939.9.1.1.5.0
ASCII text: firmware message
incl. version
subsystemDescription
1.3.6.1.4.1.21939.9.1.1.6.0
ASCII text: Subsystem mes-
sages, if applicable
extensionBoard
1.3.6.1.4.1.21939.9.1.1.7.0
ASCII text: type of the expan-
sion board if applicable
extensionBoardVersion
1.3.6.1.4.1.21939.9.1.1.8.0
Coded version of the expan-
sion board if applicable
powerBoardVersion
1.3.6.1.4.1.21939.9.1.1.9
Coded version of the PSU
board if applicable
Table 43: Objects of the group abb->abbMgmt->system->version
Object name
Read object
Write object
sensorDetected
1.3.6.1.4.1.21939.9.1.2.1.1.0
Temperature sensor
detected:
–notdetected (0)
–detected (1)
actualTemperature
1.3.6.1.4.1.21939.9.1.2.1.2.0
Device temperature as inte-
ger
minimalTemperature
1.3.6.1.4.1.21939.9.1.2.1.3.0
Lowest device temperature
ever as integer
minimalTemperatureTime-
stamp
1.3.6.1.4.1.21939.9.1.2.1.4.0
Time of the lowest tempera-
ture as SNTP seconds or zero
maximalTemperature
Highest device temperature
ever as integer
Table 44: Objects of the group abb->abbMgmt->system->enviroment->temperature