Functions
IEC 60870-5-101 and IEC 60870-5-104
Type ids IEC-101 / IEC-104
Message
direc-
tion /
Monitor
direction
Conver-
sion to
IEC-104
type id
iec104
convert
types
(Stan-
dard)
Message
direc-
tion /
Monitor
direction
Conver-
sion to
IEC-104
type id
iec101
convert
no asdu-
types
49
C_SE_NB_1
Target value setting com-
mand, scaled value
62
49
50
C_SE_NC_1
Target value setting com-
mand, floating point with
single accuracy
63
50
51
C_BO_NA_1
Bit pattern command 32 bit 64
51
52-57
TYPE_52-57
Reserved (standard range)
52-57
52-57
58
C_SC_TA_1
Single command with time
stamp CP56Time2a
58
58
59
C_DC_TA_1
Double command with time
stamp CP56Time2a
59
59
60
C_RC_TA_1
Level setting command with
time stamp CP56Time2a
60
60
61
C_SE_TA_1
Level setting command,
standardized value with time
stamp CP56Time2a
61
61
62
C_SE_TB_1
Level setting command,
scaled value with time stamp
CP56Time2a
62
62
63
C_SE_TC_1
Target value setting com-
mand, floating point with
single accuracy and time
stamp CP56Time2a
63
63
64
C_BO_TA_1
Bit pattern command
32 bit with time stamp
CP56Time2a
64
64
65-69
TYPE_65-69
Reserved (standard range)
65-69
65-69
70
M_EI_NA_1
End of initialization
70
70
71-99
TYPE_71-99
Reserved (standard range)
71-99
71-99
100
C_IC_NA_1
(general, station) polling
command
100
100
101
C_CI_NA_1
Counter query command
101
101
102
C_RD_NA_1
Polling command
102
102
103
C_CS_NA_1
Time synchronization com-
mand
103
103
Table 36: Type conversion in message direction
1KGT151021
V000 1