10-2 Parameter Definitions
MN448
Parameters in the Short parameter mode
No.
Name/Value
e
Description
Default
11 REFERENCE SELECT
Selects the reference input source for the drive
1103
PRIMARY COMMAND SOURCE
MODE
See Chapter 9 Control Modes for 1103 parameter selection details
0
0: TERMINAL CONTROL.
The drive responds directly to signals applied to the control terminals.
1:
UNI-DIRECTIONAL KEYPAD
CONTROL
The drive can be controlled in the forward direction only using an
external or remote Keypad
2:
BI-DIRECTIONAL KEYPAD
CONTROL.
The drive can be controlled in the forward and reverse directions using
an external or remote Keypad. Pressing the keypad START button
toggles between forward and reverse.
3: MODBUS NETWORK
CONTROL.
Control via Modbus RTU (RS485) using the internal accel / decel ramps
4: MODBUS NETWORK
CONTROL.
Control via Modbus RTU (RS485) interface with accel / decel ramps
updated via Modbus
5:
PI CONTROL
User PI control with external feedback signal
6:
PI ANALOG
SUM CONTROL.
PI control with external feedback signal and summation with analog
input 1
12 CONSTANT SPEEDS
Constant speeds. Constant speed activation overrides the external
speed reference. Constant speed selections are ignored if the drive is
in the local control mode.
Preset Speeds / Frequencies selected by digital inputs depending on
the setting of Parameter
9902
DIGITAL INPUTS FUNCTION SELECT.
See Chapter 9 for details on configuration of the digital inputs.
Note:
9908
= 0, the values are entered as Hz.
9908
> 0, the values are entered as RPM.
Negative value reverses direction of motor rotation.
Momentary input functions as a jog command.
1202
PRESET SPEED 1
/ JOG FREQUENCY
Defines constant speed 1 (that is the drive output frequency)
6.0Hz/RPM
2007…-2008
Output Frequency
1203
PRESET SPEED 2
/ JOG FREQUENCY
Defines constant speed 2 (that is the drive output frequency)
12.0Hz/RPM
2007…-2008
Output Frequency
1204
PRESET SPEED 3/
/ JOG FREQUENCY
Defines constant speed 3 (that is the drive output frequency)
18.0Hz/RPM
2007…-2008
Output Frequency
13 ANALOG INPUTS
Analog input signal offset
1301
ANALOG INPUT 1 OFFSET
Sets an offset, as a percentage of the full-scale range of the input,
which is applied to the analog input signal
0.0%
-500…500 %
Value in percent of the full-scale range of the input.
The OFFSET is subtracted from the ANALOG INPUT.
Example:
Analog Input 0-10V 1301 Analog Offset = 20%
Analog Level 7 V
Results:
Analog Input level (%) = 7/10 = 70%
Result = 70-20 (%) = 50%
Содержание EC Titanium ECS100A1H1DF4
Страница 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Страница 10: ...1 4 Introduction MN448 ...
Страница 20: ...3 4 Mechanical Information and Mounting MN448 ...
Страница 26: ...4 6 Electrical Installation and Planning MN448 ...
Страница 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Страница 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Страница 44: ...8 4 Parameter Navigation and Groups MN448 ...
Страница 51: ...9 7 Control Modes MN448 ...
Страница 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Страница 99: ...A 12 Modbus RTU Example Connection MN448 ...
Страница 102: ......