Quick Startup Guide 7-1
MN448
Chapter 7
Quick Startup Guide
This chapter contains Quick Start information that allows first time users to quickly and easily configure the EC Titanium for
operation in either Terminal (Hardwired) or Keypad Control. The step by step instructions will have the EC Titanium running
in a matter of minutes. Refer to Chapter 8 for Program Navigation and Chapter 10 for a complete list of the drive parameters
along with their definitions and default values.
The parameters can be accessed and programmed either through the keypad or through the EC Titanium PC Software Tool
(refer to Chapter 6 Keypad Operation), PC Software Tools to be a future release.
7.1 Quick Start Terminal Control
When delivered, the EC Titanium software parameters are in the factory default state, except for the motor data which was
pre-loaded at the factory with parameters that are optimum for the performance of the Motor. A full list of parameters &
default values can be found in Chapter 10.
Step 1
Perform Mechanical and Electrical installation as per Chapters 3 and 4.
4
5
6
7
1
2
3
Terminal mode 1103 = 0, 2-Wire Control 9902 = 0
+10V Output
Analog Speed Ref
0V
+24V Output
0: Stop (disable)
C: Run (enable)
0: Stop (disable)
C: Run (enable)
0: Forward
C: Reverse
0: Analog Speed Ref
C: Preset Speed 1
Step 2
Connect the Remote Keypad as per Chapter 5.
Factory Default Settings (no programming change required)
9902 Digital Input Function Select
1103 Command Source Mode
= 0
= 0 (Terminal Control)
Step 3
Connect a control switch between the control terminals 1 and 2 and
ensure that the contact is open (drive disabled).
Step 4
Connect a potentiometer (1kΩ min to 10 kΩ max) between terminals
5 and 7 with the wiper to terminal 6 of the control terminal.
Step 5
With the potentiometer set to zero, switch on the supply to the
EC Titanium. The display will show
SToP
.
Step 6
By default, motor setup parameters have been loaded at the factory.
If the drive has been reset to factory defaults proceed to Section 7.2
Enter Motor Data or skip to step 7.
Step 7
Close the control switch, terminals 1-2. The drive is now ‘enabled’ and the output frequency/speed are con-
trolled by the potentiometer. The display shows zero speed in Hertz as
H 0
.
0
.
with the potentiometer turned
to minimum. If the display is not showing H, change it using the
(Navigate) key.
Step 8
Turn the potentiometer to maximum. The motor will accelerate to 60Hz (the default value of parameter 2008
MAXIMUM FREQUENCY / SPEED LIMIT) under the control of the accelerating ramp time parameter 2202 AC-
CELERATION RAMP TIME. The display shows
H60
.
0
at max speed.
Step 9
The drive can display Amps, Hertz and Power (HP) in its default configuration. To change the real time operat-
ing display, briefly press the
(Navigate) key. Motor current
A 0
.
0
.
(A) will be displayed. Briefly press the
(Navigate) key a second time to cycle through available displays.
To change the display from Motor Hertz to display estimated motor speed (RPM), motor nameplate speed
(RPM) must be entered in 9908 Motor Rated Speed. When 9908 = 0 the display will show (HZ).
Step 10
STOP the motor, disable the drive by opening the control switch (terminals 1-2).
CAUTION: If the potentiometer is turned to zero with the enable closed, the display will show
H 0
.
0
.
. The drive is
still active waiting for a speed reference to re-accelerate. If left at zero reference for >= 20 seconds the
drive will go into standby mode, display shows
StandbY
, waiting for a speed reference signal.
Содержание EC Titanium ECS100A1H1DF4
Страница 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Страница 10: ...1 4 Introduction MN448 ...
Страница 20: ...3 4 Mechanical Information and Mounting MN448 ...
Страница 26: ...4 6 Electrical Installation and Planning MN448 ...
Страница 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Страница 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Страница 44: ...8 4 Parameter Navigation and Groups MN448 ...
Страница 51: ...9 7 Control Modes MN448 ...
Страница 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Страница 99: ...A 12 Modbus RTU Example Connection MN448 ...
Страница 102: ......