Control Modes 9-4
MN448
9.2.2 Terminal Control Mode 3-Wire Control Start / Stop with Forward / Reverse
Terminal Control Mode (1103 = 0), Digital Input Function Select (9902 = 11)
This is the digital input configuration when the drive is controlled using momentary push-buttons. It provides a general
purpose I/O setup with a momentary input for start, forward / reverse, stop interlock and an analog speed reference.
9902 = 11
3-Wire Forward Reverse
A momentary input on terminal 2 will start the drive
in the forward direction with a closed input on
terminal 3.
A momentary open input to I/O terminal 3 will stop
the drive as specified in 2101 (Stop Mode).
A momentary input on terminal 4 will reverse the
drive direction.
9.2.3 Terminal Control Mode Motor Thermistor Trip
Terminal Control Mode (1103 = 0), Digital Input Function Select (9902 = 3)
This is the digital input configuration when an externally motor thermistor is to be used as an overload trip input to the drive,
connect as follows. It provides a general purpose I/O setup with a hard wired start / stop enable, thermistor input and a
selection between an analog speed reference or preset speed input.
9902 = 11
3-Wire Forward Reverse
Active input across terminal 1 & 2 will cause the
drive to run.
Closing terminal 3 will force operation at preset
speed 1 (parameter 1202) or function as a jog
command.
Terminal 4 will function as a motor thermistor trip
input as defined below.
Note: When PTC motor thermistor is used,
1304
must set to
Ptc-th
mode. Otherwise digital input 3 will be used
as external trip input (digital level sensitive). When
1304
is set to
Ptc-th
, drive will display code
-Ptc
if
thermistor value is larger than 2.5k ohm. The trip can only be reset if the thermistor value drops below 1.9k
ohm. Thermistor must be connected between terminal 1 (24V DC) and terminal 4 (2nd analog input). If
1304
is
set to other value, the input will be used as external trip trigger input and drive will display code
E-trp
instead
if the input is open.
E-trp
only happens when drive is enabled (running), however thermistor trip can happen
at any time.
4
5
6
7
1
2
3
Digital Input 3
+10 Volts
Analog Input
0 Volts
+24V User Input
Digital Input 1
Digital Input 2
Start
Direction
Stop
4
5
6
7
1
2
3
Stop - Run
Thermistor
Analog - Preset 1
Digital Input 3
+10 Volts
Analog Input
0 Volts
+24V User Input
Digital Input 1
Digital Input 2
Содержание EC Titanium ECS100A1H1DF4
Страница 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Страница 10: ...1 4 Introduction MN448 ...
Страница 20: ...3 4 Mechanical Information and Mounting MN448 ...
Страница 26: ...4 6 Electrical Installation and Planning MN448 ...
Страница 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Страница 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Страница 44: ...8 4 Parameter Navigation and Groups MN448 ...
Страница 51: ...9 7 Control Modes MN448 ...
Страница 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Страница 99: ...A 12 Modbus RTU Example Connection MN448 ...
Страница 102: ......