5-2 Control Pad Wiring and Keypad Interface
MN448
5.3 Remote Panel Interface
The REMOTE PANEL uses a standard RJ45 6-Way connector as its electrical interface, which provides a simple solution for
the user to setup their system using a standard RJ45 6-Way data cable. The signal layout of the connector is as follows:
CAN -
CAN +
0 Volts
-RS485 (PC)
+RS485 (PC)
+24 Volt
-RS485 (Modbu RTU)
+RS485 (Modbus RTU)
1
2
3
4
5
6
7
8
This is not an Ethernet
connection. Do not connect
directly to an Ethernet port.
Warning:
5.3.1 Cable Requirements
If the data cable is made up on site, ensure that the connection pin out is correct: Pin 1 to Pin 1, Pin 6 to Pin 6, etc.
Figure 5-2 8-way ribbon cable with header
1
1
CAUTION: Incorrect cable connection may damage the drive. Extra care should be taken when using third party
cable.
Содержание EC Titanium ECS100A1H1DF4
Страница 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Страница 10: ...1 4 Introduction MN448 ...
Страница 20: ...3 4 Mechanical Information and Mounting MN448 ...
Страница 26: ...4 6 Electrical Installation and Planning MN448 ...
Страница 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Страница 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Страница 44: ...8 4 Parameter Navigation and Groups MN448 ...
Страница 51: ...9 7 Control Modes MN448 ...
Страница 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Страница 99: ...A 12 Modbus RTU Example Connection MN448 ...
Страница 102: ......