Troubleshooting 13-3
MN448
13.4 Drive Module Fault Codes
In the event of a trip, the following potential codes can be accessed from the remote keypad. The fault code will be shown
and the fault no. will be transferred in the high byte of the drive status word when an external serial communication is used.
Table 13-2 Remote Keypad Fault Codes
Fault
Code
No.
Description
Corrective Action
Stop
0x00
Drive is READY and in a stopped condition. The motor is not energized. No enable signal is present to
start the drive
p-de
0X0A
Factory Default
parameters have been
loaded
Press the STOP key, drive is ready to configure for particular application
000
0x03
Instantaneous Over
Current
Excess load or shock load
on the motor
Fault occurs immediately on drive enable or run command
Check the output wiring connections to the motor and the motor for short
circuits phase to phase and phase to earth.
Fault occurs during motor starting
Check the motor is free to rotate and there are no mechanical blockages.
Ensure the motor nameplate current is correctly entered in parameter
9906
.
Increase acceleration time in parameter
2202
. Reduce motor boost voltage
setting in parameter
2603
.
Fault occurs when motor operating at constant speed
Investigate overload.
Fault occurs during motor acceleration or deceleration
Accel/Decel times are too short, increase the value of parameter
2202
or
2203
0009
0x04
Motor thermal overload
protection trip
The drive has tripped after
delivering >100% of value
in 9906 for a period of
time to prevent damage to
the motor.
Ensure the correct motor nameplate current value is entered in parameter
9906. Check for correct Star or Delta wiring configuration. Check to see
when the decimal points are flashing (which indicates the output current >
parameter 9906 value) and either increase acceleration ramp (parameter
2202) or decrease motor load. Check the total motor cable length is within
the drive specification. Check the load mechanically to ensure it is free, and
that no jams, blockages or other mechanical faults exist
0004
0x05
Hardware Over Current
Check the wiring to motor and the motor for phase to phase and phase to
earth short circuits. Disconnect the motor and motor cable and retest. If the
drive trips with no motor connected, it must be replaced and the system fully
checked and retested before a replacement unit is installed.
000
0x06
Over voltage on DC bus
Check the supply voltage is within the allowed tolerance for the drive. If the
fault occurs on deceleration or stopping, increase the deceleration time in
parameter 2203 or install a suitable brake resistor and activate the dynamic
braking function with parameter 2020
0006
0x07
Under voltage on DC bus
The incoming supply voltage is too low. This trip occurs routinely when power
is removed from the drive. If it occurs during running, check the incoming
power supply voltage and all components in the power feed line to the drive.
0003
0x08
Heatsink over temperature
The drive is too hot. Check the ambient temperature around the drive is within
the drive specification. Ensure sufficient cooling air is free to circulate around
the drive.
Increase the panel ventilation if required. Ensure sufficient cooling air can
enter the drive, and that the bottom entry and top exit vents are not blocked
or obstructed.
U-T
0x09
Under temperature
Trip occurs when ambient temperature is less than -10°C. The temperature
must be raised over -10°C in order to start the drive.
00
0x10
Faulty thermistor on
heatsink.
Refer to your local ABB representative
O-hEAt
0x17
Drive internal temperature
too high
Drive ambient temperature too high, check adequate cooling air is provided
Содержание EC Titanium ECS100A1H1DF4
Страница 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Страница 10: ...1 4 Introduction MN448 ...
Страница 20: ...3 4 Mechanical Information and Mounting MN448 ...
Страница 26: ...4 6 Electrical Installation and Planning MN448 ...
Страница 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Страница 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Страница 44: ...8 4 Parameter Navigation and Groups MN448 ...
Страница 51: ...9 7 Control Modes MN448 ...
Страница 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Страница 99: ...A 12 Modbus RTU Example Connection MN448 ...
Страница 102: ......