12-2 Technical Data
MN448
12.5 Digital & Analog I/O
Digital Inputs Specification
Voltage Range
8 – 30 V dc, Internal or External supply, NPN (positive logic)
Response Time
< 8ms
Analog Inputs Specification
Range
Current:
0-20mA, 4-20mA. 20mA max input current
Voltage:
-10-10V (Analog Input 1 Only), 0-10V, 0-5V, 0/24V, 30V max input
Resolution
Analog Input 1:
12-bit, <16ms response time (Uni-Polar)
Analog Input 2:
12-bit, <16ms response time (Uni-Polar)
Impedance
Current Mode:
500R
Voltage Mode:
> 100kR
Accuracy
Better than 1% of full scale
Scaling & Offset
Parameter adjustable
Analog Output Specification
Range
Current:
0...20mA, 4...20mA, 20mA max
Analog:
0..10V, 0 / 24V (digital), 20mA max
Resolution
10-bit
Accuracy
better than 1% of full scale
Relay Output
Max Switching
Voltage:
250VAC, 30 VDC
Max Switching
Current:
5A at 30 Volt DC, 6A at 250 Volt AC
Response Times
Command Source
Response Time
Digital Input
<8ms
Analog Input
<16ms
Modbus RTU Interface
<8ms from receipt of valid command
CAN Interface
<8ms from receipt of valid command
Master / Slave Function
<8ms, response, 60ms cycle
Power Stage
<10ms to enable output
12.6 Output Current Limit
Overload Operation
EC Titanium provides the following maximum permissible overload current:
• 150% Output current / 60 Seconds Maximum
• 175% Output current / 2.5 Seconds Maximum
Maximum continuous output current and maximum permissible overload time may be adjusted according to the
following:
• PWM Switching Frequency Selected
• Low Output Frequency
• High Ambient Temperature
Содержание EC Titanium ECS100A1H1DF4
Страница 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Страница 10: ...1 4 Introduction MN448 ...
Страница 20: ...3 4 Mechanical Information and Mounting MN448 ...
Страница 26: ...4 6 Electrical Installation and Planning MN448 ...
Страница 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Страница 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Страница 44: ...8 4 Parameter Navigation and Groups MN448 ...
Страница 51: ...9 7 Control Modes MN448 ...
Страница 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Страница 99: ...A 12 Modbus RTU Example Connection MN448 ...
Страница 102: ......