13-4 Troubleshooting
MN448
Fault
Code
No.
Description
Corrective Action
004
0x0B
External trip
(on digital input 3)
E-trip requested on control input terminals. Some settings of parameter 9902
DIGITAL INPUTS FUNCTION SELECT require a normally closed contactor to
provide an external means of tripping the drive in the event that an external
device develops a fault. If a motor thermistor is connected check if the motor
is too hot.
00
0x0C
Comms loss trip
Check communication link between drive and external devices. Make sure
each drive in the network has its unique address.
00
0x0E
Input phase loss trip
Drive intended for use with a 3 phase supply has lost one input phase
SPIn-
0x0F
Spin start failed
Spin start function failed to detect the motor speed.
00
0x11
Internal memory fault.
Parameters not saved, defaults reloaded.
Try again. If problem recurs, refer to your local ABB representative
000
0x12
Analog input current out
of range
Check input current in range defined by parameter 1300.
00
-
Internal drive Fault
Refer to your local ABB representative
AUty
-
Internal drive Fault
Refer to your local ABB representative
Содержание EC Titanium ECS100A1H1DF4
Страница 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Страница 10: ...1 4 Introduction MN448 ...
Страница 20: ...3 4 Mechanical Information and Mounting MN448 ...
Страница 26: ...4 6 Electrical Installation and Planning MN448 ...
Страница 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Страница 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Страница 44: ...8 4 Parameter Navigation and Groups MN448 ...
Страница 51: ...9 7 Control Modes MN448 ...
Страница 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Страница 99: ...A 12 Modbus RTU Example Connection MN448 ...
Страница 102: ......