Quick Startup Guide 7-3
MN448
7.4 Quick Start Keypad Control
When delivered, the EC Titanium software parameters are in the factory default state, except for the motor data which was
pre-loaded at the factory with parameters that are optimum for the performance of the Motor. A full list of parameters &
default values can be found in Chapter 10.
Step 1
Perform Mechanical and Electrical installation as per Chapters 3 and 4.
Step 2
Connect the Remote Keypad as per Chapter 5.
Step 3
Set 1103 Primary Command Source = 1 to allow the EC Titanium to be controlled from the keypad in a for-
ward direction only, or = 2 to allow forward and reverse operation.
Step 4
Reference Chapter 6 on details on how to navigate the keypad.
Step 5
Connect a control switch between the control terminals 1 and 2 ensuring that the contact is open (drive dis-
abled).
Step 6
Switch on the supply to the EC Titanium, Press and hold the
navigate key for > 1 second to enter
parameter view mode and set Parameter 1103 Primary Command Source Mode = 1 or 2.
Step 7
Enable the drive by closing the switch between control terminals 1 & 2.
The keypad display will show
SToP
.
Step 8
Press the
(Stop) key, the display shows
H 0
.
0
.
. and the last digit should be flashing.
The value of the digital potentiometer will be displayed, indicating the target speed.
Use the
(Up) and
(Down) keys to select the required target speed.
Press the STOP key to return to the real time display showing “
SToP
”.
Step 9
Press the
(Start) key to start the drive ramping up to the target speed. The drive will run forward,
increasing speed until the target speed is reached. During operation the speed of the drive can be changed in
real time by simply using the
(Up) and
(Down)arrows.
Step 10
STOP the motor, PRESS the (Stop) Key and disable the drive by opening the control switch (terminals 1-2).
CAUTION: If the potentiometer is turned to zero with the enable closed, the display will show
H 0
.
0
.
. The drive is
still active waiting for a speed reference to re-accelerate. If left at zero reference for >= 20 seconds the
drive will go into standby mode, display shows
StandbY
, waiting for a speed reference signal.
Reverse Direction of Rotation (Parameter 1103 = 2)
While in operation press the
(Start) key. The motor will reverse its direction of rotation. Target speed will be the same
as set in the forward direction unless the Up or Down arrows change the set speed value.
CAUTION: Whenever the drive is started, it will start with a positive speed unless the direction is negated by the
digital inputs on the user terminals. See Chapter 9 Control Modes for setup instructions.
Содержание EC Titanium ECS100A1H1DF4
Страница 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Страница 10: ...1 4 Introduction MN448 ...
Страница 20: ...3 4 Mechanical Information and Mounting MN448 ...
Страница 26: ...4 6 Electrical Installation and Planning MN448 ...
Страница 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Страница 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Страница 44: ...8 4 Parameter Navigation and Groups MN448 ...
Страница 51: ...9 7 Control Modes MN448 ...
Страница 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Страница 99: ...A 12 Modbus RTU Example Connection MN448 ...
Страница 102: ......