10-4 Parameter Definitions
MN448
10.2 Long Parameter Group
The following tables describes the parameters that are visible in the
PA-
mode (Long Group Parameters) that contain a
sequential listing of all available parameters.
Parameters in the Long parameter mode
No.
Name/Value
Description
Default
0000
READ ONLY PARAMETERS
Pressing the NAVIGATE key when the
0000
parameter is displayed will
enter into the Read only status parameter list shown below. Initially
00
is shown and using the UP and DOWN Arrows will scroll to the required
Read only status parameter. Pressing NAVIGATE once more on the will then
display the value of that particular Read only status parameter.
For those parameters which have multiple values (e.g. software ID
parameter 3301), pressing the UP and DOWN keys will display the different
values within that parameter.
Pressing NAVIGATE returns to the next level up. If NAVIGATE is then
pressed again (without pressing UP or DOWN), the display changes to the
next level up (main parameter level, i.e. Parameter “
0000
”).
Fault history
(read-only)
0102
Rotor Speed
(Estimated)
In vector control mode, this parameter displays the estimated rotor speed
of the motor.
0104
Motor Current
8 most recent values prior to trip, updated every 250ms
0107
DC BUS VOLTAGE
Displays the instantaneous DC Bus Voltage internally within the drive in V
DC. (0…1000V dc)
0109
APPLIED MOTOR VOLTAGE
Displays the instantaneous output voltage from the drive to the motor V AC.
(0…600V AC)
0110
INTERNAL HEATSINK
TEMPERATURE
Temperature of heatsink in °C (-20 … 100 °C)
0111
SPEED REFERENCE INPUT
Displayed in Hz if Parameter 9908 MOTOR RATED SPEED = 0, otherwise
displayed in RPM. (-2008 … 2008)
0115
KWh/MWh METER
Total number of KWh/MWh consumed by the drive.
0120
ANALOG INPUT 1 APPLIED
SIGNAL LEVEL
Displays the signal level applied to analog input 1 (Terminal 6) in % after
scaling and offsets have been applied.
0121
ANALOG INPUT 2 APPLIED
SIGNAL LEVEL
Displays the signal level applied to analog input 2 (Terminal 4) in % after
scaling and offsets have been applied.
0126
PI CONTROLLER OUTPUT
Displays the output level of the PI controller in %.
0140
HOURS RUN METER
Not affected by resetting factory default parameters.
(0 to 99 999 hours)
0150
INTERNAL DRIVE
TEMPERATURE
Actual internal ambient temperature in °C
0160
DIGITAL INPUT STATUS
Binary value.
Displays the status of the drive inputs, starting with the left hand side digit
= Digital Input 1 etc.
0183
DC BUS VOLTAGE RIPPLE
LEVEL
Displays the level of ripple present on the DC Bus Voltage in V DC. This
parameter is used by the ACS255 for various internal protection and
monitoring functions.
0188
OPERATING TIME
ACCUMULATED WITH
HEATSINK TEMPERATURE
ABOVE 85°C
Displays the amount of time in hours and minutes that the ACS255 has
operated for during its lifetime with a heatsink temperature in excess of
85°C. This parameter is used by the ACS255 for various internal protection
and monitoring functions. (HH:MM:SS)
0189
OPERATING TIME
ACCUMULATED WITH
AMBIENT TEMPERATURE
ABOVE 80°C
Displays the amount of time in hours and minutes that the DRIVE
has operated for during its lifetime with an ambient temperature in
excess of 80°C. This parameter is used by the DRIVE for various
internal protection and monitoring functions. (HH:MM:SS)
Содержание EC Titanium ECS100A1H1DF4
Страница 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Страница 10: ...1 4 Introduction MN448 ...
Страница 20: ...3 4 Mechanical Information and Mounting MN448 ...
Страница 26: ...4 6 Electrical Installation and Planning MN448 ...
Страница 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Страница 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Страница 44: ...8 4 Parameter Navigation and Groups MN448 ...
Страница 51: ...9 7 Control Modes MN448 ...
Страница 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Страница 99: ...A 12 Modbus RTU Example Connection MN448 ...
Страница 102: ......