10-16 Parameter Definitions
MN448
10.3 Advanced Parameter Group
The following tables describes the parameters that are visible in the
PA-A
mode (Advanced Parameters).
Parameters in the Long parameter mode
Index
Name/Selection
Description
Default
2017
Maximum Current Limit
Defines the max current limit in vector control modes.
110 %
0.1…175.00
2105
DC Injection Speed
Sets the speed at which DC injection current is applied during braking to
Stop, allowing DC to be injected before the drive reaches zero speed if
desired.
0.0 Hz/Rpm
0.0…2008
2106
DC Injection Current
Sets the level of DC injection braking current applied according to the
conditions set in 2104 and 2105.
20 %
0.0…100.0
2301
Vector Mode Gain
Single Parameter for Vector speed loop tuning. Affects P & I terms
simultaneously. Not active when
9903
= 1.
50 %
0.0…200.0
2605
Operating Mode Select
Provides a quick set up to configure key parameters according to the
intended application of the drive. Parameters are preset according to the
table.
Setting Application
Current
Limit (2017)
Torque
Characteristic
(2610 & 2611)
Spin Start
(2101)
0
General
150%
Constant
0: Off
1
Pump
110%
Variable
0: Off
2
Fan
110%
Variable
2: On
2
0: Industrial Mode
Intended for general purpose applications.
1: Pump Mode
Intended for centrifugal pump applications.
2: Fan Mode
Intended for Fan applications.
9903
Motor Control Mode
Selects the motor control method. For proper control of the EC
Titanium parameter
9903
should be set to 2 (PM Control).
2
0
Vector speed control mode
1
V/HZ Mode
2
PM Motor Vector Speed Control
3
BLDC Motor Vector Speed Control
9910
Motor parameter
Autotune
WARNING:
Autotune should not
be performed on this
product.
Autotune is disabled in the ECM software however it can be
accessed through the keypad.
In the event an Autotune is performed it will affect performance and
possibly make the IMD inoperable. To recover the motor specific
parameters will need to be loaded. The necessary parameters
and their values can be obtained by scanning the QR Code on the
motor with a smart device or you can access the parameters from
the ECM software under the File menu (allows the parameter set to
be downloaded from the web).
WARNING:
Autotune should not be performed on this product.
0: Disable
0: Disable
1: Enable
Drive immediately carries out a non-rotating autotune, parameter
9910
MOTOR PARAMETER AUTO-TUNE ENABLE returns to 0
when completed.
Содержание EC Titanium ECS100A1H1DF4
Страница 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Страница 10: ...1 4 Introduction MN448 ...
Страница 20: ...3 4 Mechanical Information and Mounting MN448 ...
Страница 26: ...4 6 Electrical Installation and Planning MN448 ...
Страница 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Страница 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Страница 44: ...8 4 Parameter Navigation and Groups MN448 ...
Страница 51: ...9 7 Control Modes MN448 ...
Страница 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Страница 99: ...A 12 Modbus RTU Example Connection MN448 ...
Страница 102: ......