POINT SETPOINT
BLOCK
OBJECTNAME
DESCRIPTION
UNITS AND DEFAULT VALUES
IMPERIAL STG.
METRIC STG.
237
Yes
PriAirPIDInteg (A237) with Actuator
Primary air PID integral
100
no-units
100
no-units
237
Yes
PriAirPIDInteg (A237) without Actuator
Primary air PID integral
180
no-units
180
no-units
238
Yes
Fusion_Offset(A238) without Actuator
The maximum adjustment of the
setpoint range for the FusionAir
sensor. (FA Variants only)
5
°F
5
°c
239
Yes
Fusion_StptStepSize (A239) without
Actuator
The amount of degrees the setpoint
is adjusted with every button press
on the FusionAir sensor. (FA Variants
only)
.5
°F
.5.
°c
240
Yes
CustomOpenVX10_AO15 (A240)
AO15 Open Value Custom = Volts X
10]
50
%
50
%
241
No
AO15DisplayPos (A241)
AO15 display value 0
…
100%
0
%
0
%
242
Yes
InputConfigA (A242)
VAV box configuration setpoint
0
no-units
0
no-units
243
Yes
OutputConfigA (A243)
VAV box configuration setpoint
-71
no-units
-71
no-units
244
Yes
PriAirMaxMult (A244)
Max Flowrate Air Multiplier
1
no-units
1
no-units
245
Yes
Fusion_altCO2Input
Analog value to send a remote CO
₂
sensor value to the FusionAir Stat.
(FA Variants only)
0
ppm
0
ppm
246
Yes
PriAirPIDDeriv (A246) with Actuator
Primary Air PID derivative
0
no-units
0
no-units
246
Yes
PriAirPIDDeriv (A246) without Actuator
Primary Air PID derivative
0
no-units
0
no-units
247
Yes
CustomClosedVX10_AO14 (A247)
AO14 Open Value Custom = Volts X 10
0
%
0
%
248
Yes
CustomOpenVX10_AO14 (A248)
AO14 Open Value Custom = Volts X 10
50
%
50
%
249
Yes
TABPriAirEffMinStpt (A249)
Current effective minimum CFM
setpoint. Will read min heat CFM, min
cool CFM, or 0.
cfm
L/s
253
Yes
UI04CO2SensorBase (A253)
CO
2
Sensor Reading at 0 V DC
0
ppm
0
ppm
254
Yes
UI04CO2SensorSpan (A254)
CO
2
Sensor Reading at 10 V DC
2000
ppm
2000
ppm
255
Yes
LocalCO2Stpt (A255)
Net Zone CO
2
Setpoint
500
ppm
500
ppm
256
Yes
UI04SensorBase (A256)
Relative Humidity Sensor Reading at
0 V DC
0
%RH
0
%RH
257
Yes
UI04SensorSpan (A257)
Relative Humidity Sensor Reading at
10 V DC
100
%RH
100
%RH
258
Yes
LocalDehumidStpt (A258)
Zone Dehumidification Setpoint
65
%RH
65
%RH
259
Yes
CommunicationsOfflineTimer (A259)
Amount of minutes before
communication status has been
considered off when BACnet
communications point
enabled.
15
min
15
min
260
Yes
InputConfigB (A260)
VAV box configuration setpoint
0
no-units
0
no-units
261
Yes
OutputConfigB (A261)
VAV box configuration setpoint
0
no-units
0
no-units
263
No
EffZoneOccHeatStpt (A263)
Zone Effective Occupied Heat
Setpoint
0
°F
0
°C
264
No
EffZoneOccCoolStpt (A264)
Zone Effective Occupied Cool
Setpoint
0
°F
0
°C
271
No
ZATError (A271)
Zone Temp Error from Heating and
Cooling Setpoints
0
°F
0
°C
281
No
TriStateHtVlvPos (A281)
Current valve position if tristate heat
valve is used
0
…
100%
0
%
0
%
286
Yes
AOConfigD (A286)
VAV box configuration setpoint
0
no-units
0
no-units
296
Yes
DamperDegrees
CBV-2U4-3T-N
only
90
deg
90
deg
297
Yes
DampActDriveTime
CBV-2U4-3T-N
only
95
sec
95
sec
313
No
DamperPosition (A313)
Current damper position (CBV-2U4-
3T-N only)
0
%
0
%
320
Yes
TriStateHtVlvDriveTime (A320)
Tristate valve travel time in seconds
95
sec
95
sec