CBV-2U4-3T(-N) |
Appendix : List of CBV-2U4-3T(-N) points
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
65
M
AN0
13
9
re
v
14
POINT SETPOINT
BLOCK
OBJECTNAME
DESCRIPTION
UNITS AND DEFAULT VALUES
IMPERIAL STG.
METRIC STG.
during unoccupied mode. (FA
Variants only)
208
No
PriAirModeEnumeration (A208)
Numerated value of primary air mode
state.
0 = On
1 = Off
3 = Fire stop
0
no-units
0
no-units
210
Yes
TABPriAirDbandStpt (A210)
Primary air control dead band
Flowrate setpoint. This point
supports priority array.
50
CFM
25
l/sec
211
Yes
TABPriAirMaxStpt (A211)
Primary air maximum Flowrate
setpoint. This point supports priority
array.
800
CFM
400
l/sec
212
Yes
TabPriAirMaxHgtStpt (A212)
Primary air max heating Flowrate
setpoint. This point supports priority
array.
50
CFM
25
l/sec
214
Yes
Fusion_Offset(A214) with Actuator
The maximum adjustment of the
setpoint range for the FusionAir
sensor. (FA Variants only)
5
°F
5
°c
215
KFactorOut (A215)
Displays the current calculated K-
factor
CFM@1”
l/sec@1Pa
216
Yes
Fusion_StptStepSize (A216) with
Actuator
The amount of degrees the setpoint
is adjusted with every button press
on the FusionAir sensor. (FA Variants
only)
.5 °F
.5.
°c
218
Yes
MeasuredFlow/K (A218)
When KFactSelect (D204) is True,
input measured flow from balancer.
When KfactSelect (D204) is False,
input factory K-factor
219
No
PriDamperCmdEnumeration (A219)
Enumerated value for damper
command state
0 = Off
1 = Open
2 = Close
4 = Close Flowrate high for series fan
8 = Open manual
16 = Close manual
32 = Closed fire stop
0
no-units
0
no-units
221
Yes
CBT_STAT_CFG (A221)
Enumerated value for CBT-Stat
operation
0-None
1-OccOvrd
2-Temp Setpoint Adj
3-OccOvrd & Temp Setpoint Adj
4-Perm Setpnt Adj
5-OccOvrd & Perm Setpnt Adj
3
no-units
3
no-units
224
Yes
TABFanDbandStpt (A224)
Minimum variable fan speed
command setpoint
0
%
0
%
225
Yes
TABFanMaxStpt (A225)
Maximum cooling variable speed fan
command setpoint
60
%
60
%
226
Yes
TABFanHtgMaxStpt (A226)
Maximum heating variable speed fan
command setpoint
60
%
60
%
227
Yes
TABFanStandbyStpt (A227)
Variable fan speed command
setpoint when in standby mode
0
%
0
%
230
Yes
UI01_10KSensorCal (A230)
UI01 calibration offset
0
°F
0
°c
231
Yes
SetptSliderSpan (A231)
Setpoint slider span
4
°F
4
°c
232
Yes
ZonePIDGain (A232)
Zone temperature PID gain
10
no-units
10
no-units
235
Yes
HeatStateOffStpt (A235)
Temperature setpoint for setting
Primary Air State to cold when VAV
box has been configured for local
auto change over.
72
°F
21
°c
236
Yes
PriAirPIDGain (A236) with Actuator
Primary air PID gain
0.11
no-units
0.11
no-units
236
Yes
PriAirPIDGain (A236) without Actuator
Primary air PID gain
0.10
no-units
0.10
no-units