CBV-2U4-3T(-N) |
Control Sequence Overview
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
56
M
AN0
13
9
re
v
14
In order to use this feature, first identify the output controlling baseboard heat, then select
Run Only Baseboard
heat during unoccupied
. Any other heat stages will be skipped during unoccupied.
HEAT ORDER
Using the configuration spreadsheet, it is possible to choose how to stage baseboard heat in conjunction with
any box heat. This is done by first determining which type of heat is used in the box (On/Off, modulating, or
tri-state) and at the baseboard, then by making use of the following rules. A heating
strategy
may be configured
to cover most cases:
1.
Within digital and analog heat outputs, the lower output number is staged on first, and
2.
The box may be configured to run AO or DO heat (including Tri-state outputs) first, last, or
concurrently.
DIGITAL OUTPUT DIRECT/REVERSE ACTION
In the
CBV-2U4-3T(-N)
the digital outputs could also be set for reverse acting. This would be typically used for
controlling
normally-closed
heating valves.
•
(DS313)
•
•
DIGITAL OUTPUT DISPLAY POSITION
These points will display the heat command for the various digital outputs regardless if digital output(s) are
set for reverse or direct acting.
•
(D284)
•
(D305)
•
(D306)
ANALOG OUTPUT RANGE OPTIONS
The
range
of
the
AOs
include
0
…
10 V DC, 2
…
10 V DC, and custom ranges. If using custom ranges, enter them in the points listed below.
For example, to give AO14 a closed position of 6.0 V DC and an open position of 9.0 V DC, 60 would be entered
in A247 and 90 would be entered in A248.
•
(A247)
•
(A248)
•
(A157)
•
CustomOpenVX10_AO15
(A240)