Installation Overview
PREPARING TO INSTALL THE CBV-2U4-3T(-N)
This section describes how to unpack the unit and how to prepare the site for installation of the
CBV-2U4-
3T(-N)
. In order to ensure reliable operation of the controller, the installation site should meet the
requirements listed in this section.
ENVIRONMENTAL AND ELECTRICAL REQUIREMENTS
The controller’s immediate environment must meet the following specifications.
Supply Voltage:
24 V AC, 50/60Hz
Note:
One side of the 24 volts transformer must be grounded; refer to
on page 10
for more information.
Temperature:
Operating temperature is 32 °F
…
122 °F (0 °C ... 50 °C) ambient
UNPACKING THE CBV-2U4-3T(-N)
The
CBV-2U4-3T(-N)
is shipped in its own box. Multiple
CBV-2U4-3T(-N)
boxes may be packaged together in
a larger box. Upon receiving the
CBV-2U4-3T(-N)
controller shipment, immediately open and inspect the
contents. Check outside of the box for any physical damage. Contact the shipper immediately to report any
shipping-related damage to the product. ABB is not responsible for damage to the product caused by
shipping, either by a ABB -selected shipper or by a customer-specified shipping company.
INSTALLATION OF CBV-2U4-3T(-N)
PHYSICAL INSTALLATION OF CONTROLLER
When installing the
CBV-2U4-3T(-N)
controller you should consider the following:
•
Selecting a location with the appropriate clearance.
•
Determining the damper shaft diameter.
Note:
Shaft diameter must be no larger than
5/8”
(15.8 mm).
•
Determining the direction of rotation for the damper.
•
Accommodating dampers with less than a 90° actuator stroke.
•
Mounting controller.