CBV-2U4-3T(-N) |
Appendix : List of CBV-2U4-3T(-N) points
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
69
M
AN0
13
9
re
v
14
POINT SETPOINT
BLOCK
OBJECTNAME
DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
DEFAULT VALUES
IMP STG.
MET
STG.
174
Yes
FanHeatMaxMan (D174)
Fan Commanded to Max Heat Speed
Manual Mode
On
Off
0
0
175
Yes
FanStandbyMan (D175)
Fan Commanded to Standby Speed
Manual Mode
On
Off
0
0
177
Yes
DO13RemoteCmd (D177)
DO13 override on command
On
Off
0
0
178
Yes
EnableManualHeatCmd (D178)
Manual Heat Enable Command
On
Off
0
0
179
Yes
EnableManualCoolCmd (D179)
Manual Cool Enable Command
On
Off
0
0
180
No
HeatModeSts
Heat mode status
On
Off
0
0
181
No
CoolModeSts
Cool mode status
On
Off
0
0
184
Yes
OccCmd (D184)
Occupancy command
Occ
Non
Occ
1
1
185
Yes
StandbyCmd (D185)
Standby command
On
Off
0
0
186
No
OccModeSts (D186)
Occupancy mode status
Occ
Non
Occ
0
0
187
No
StandbyModeSts (D187)
Standby mode status
On
Off
0
0
188
No
OccSensorEffCmdOnBoardSwitch
(D188)
Occupancy effective command from
push button override or motion sensor
On
Off
0
0
191
Yes
DampOpenMan (D191)
Set Damper Full Open Manual Mode
On
Off
0
0
192
Yes
DampCloseMan (D192)
Set Damper Full Close Manual Mode
On
Off
0
0
193
Yes
DampMaxMan (D193)
Damper set to Max Flowrate Manual
Mode
On
Off
0
0
194
Yes
DampMinMan (D194)
Damper set to Min Flowrate Manual
Mode
On
Off
0
0
199
Yes
FireStopCmd (D199)
Damper set to Fire Stop Cmd
Enable
Disable
0
0
204
Yes
KFactSelect (D204)
True will allow measured flow to be
entered at (A218), False will allow
factory K-factor to be entered at (A218)
On
Off
0
0
208
No
LoadShedEffCmd (D208)
Load Shed Enable Effective Command
Enable
Disable
0
0
210
Yes
FanHeatMinMan (D210)
Fan Commanded to Min Heat Speed
Manual Mode
On
Off
0
0
211
Yes
LoadShedEnable (D211)
Load Shed Enable Command
Enable
Disable
0
0
213
Yes
Purge (D213)
Box damper will be overridden open.
Enable
Disable
0
0
222
No
OverrideStatus_Outputs (D222)
If any outputs have been overridden
this point will be on
On
Off
0
0
223
No
ManualStatus_Application (D223)
If any TAB manual mode override points
have been set to on this point will be on
On
Off
0
0
224
No
OverrideStatus_Inputs
(D224)
If any inputs have been overridden this
point will be
ON
On
Off
0
0
225
Yes
DamperAdaption(D225)
CBV-2U4-3T ONLY
When adaptation is selected, the
actuator will drive one full cycle to its
mechanical end-stop, and when it
reaches that point
the actuator’s
working range will be adapted to the
actual mechanical angle of rotation. To
initiate this process, toggle point D225
On
, then toggle it
Off
.
On
Off
0
0
226
No
PurgeEffCmd (D226)
If commanded to Purge mode this point
will be on
On
Off
0
0
230
Yes
DampReverse (D230)
Reverses damper action
0 = CW open, CCW close
1 = CW close, CCW open
On
Off
0
0
231
Yes
EnaUnoccCool (D231)
This point enables unoccupied cooling
Enable
Disable
1
1
232
No
IO_Application_Status
(D232)
If any input, outputs, or manual status
application mode is on, this point is on
On
Off
0
0
235
No
UI04DigitalStatusHost
(D235)
UI04 digital status host
On
Off
0
0