CBV-2U4-3T(-N) |
Control Sequence Overview
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
47
M
AN0
13
9
re
v
14
Encoding multiple commands into one group occupancy code write
To pack more than one command into the group occupancy code, add the on values of all desired on
commands.
To write Occupied and a Primary Air State of Hot Air, send the value 5 (1 for oc 4 for Primary Air
State=hot).
To write Standby and a Primary Air State of Hot Air, send the value 12 (8 for S 4 for Primary Air
State=hot).
If the desired mode is the default mode (“off value”)
, users do not need to write anything as the value is
always
0
.
Only add that value to all other on values when “on value”
is desired.
On a day to day basis, users might write occupied/unoccupied (by schedule), primary air mode command
on/off (by AHU fan status) and, if there is morning warm up or other AHU heat, Primary air state command
Cold/Hot (by AHU discharge air temp).
Note:
There are other points that can be used to put the
CBV-2U4-3T(-N)
controller into these modes. To utilize these
points the GroupXOccCode
must be set for the default setting of 1. Conversely, to use the GroupXOccCode
the following points must be set to default settings.
If the appropriate points are not set to default then
CBV-2U4-3T(-N)
may not go into the mode that it is being commanded to.
The following is a list of those
points and their default settings.
POINT NAME
DEFAULT VALUE
(D184)
1 / Occ
(D160)
0 / Enable
0 / Cooling
(D185)
0 / Off
(D211)
0 / Disable
0 / Disable
(D213)
0 / Disable
BACNET COMMUNICATIONS STATUS AND STAND-ALONE OPERATION
The
CBV-2U4-3T(-N)
has the ability to monitor its communication status with the master controller. If this feature is
enabled, the box will be put into a failsafe mode if communications are lost.
To use this feature, set point
(D257) to 1 (default is set to 0 or off). The master controller must
write a value of 1 to point
OfflineTimerCommTestValueBACnet
(A2) more frequently than the time delay setting in point
(A259) (do not use less than 5 minutes, default is 15 minutes).
After the time delay expires, if no writes are seen,
(D10) will be set to a value of 1 indicating a
communications loss.
During a communications loss state, the
CBV-2U4-3T(-N)
will be set to the following:
•
Occupied
•
Primary Air Mode: OFF
•
Primary Air State: Cool
•
Load Shed: Disabled
•
(D10) RO
(0 = Communications OK, 1 = Communications loss)
Note:
If the last command sent to the
CBV-2U4-3T(-N)
was firestop enabled before losing BACnet communications, it
will stay in this state until firestop command has been disabled.