CBV-2U4-3T(-N) |
Appendix : List of CBV-2U4-3T(-N) points
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
63
M
AN0
13
9
re
v
14
POINT SETPOINT
BLOCK
OBJECTNAME
DESCRIPTION
UNITS AND DEFAULT VALUES
IMPERIAL STG.
METRIC STG.
79
No
LocalRemoteSlaveDehumidCalc (A79)
Current dehumidification command
0
…
100%
0
%
0
%
80
Yes
Group1TABCode (A80)
Group 1 TAB code
0
no-units
0
no-units
84
Yes
OutputConfigC_Bsbd (A84)
VAV box configuration setpoint
128
no-units
128
no-units
85
Yes
Group2TABCode (A85)
Group 2 TAB code
0
no-units
0
no-units
86
No
StptSliderEffOccOffset (A86)
Current slider setpoint offset
0
°F
0
°C
87
Yes
Group3TABCode (A87)
Group 3 TAB code
0
no-units
0
no-units
88
No
EffGroupAddress (A88)
Current group address
0
no-units
0
no-units
90
Yes
Group0OccCode (A90)
Group 0 command used to put VAV box
in multiple modes of operation. This
point supports priority array.
1
no-units
1
no-units
91
Yes
Group1OccCode (A91)
Group 1 command used to put VAV box
in multiple modes of operation. This
point supports priority array.
1
no-units
1
no-units
92
Yes
Group2OccCode (A92)
Group 2 command used to put VAV box
in multiple modes of operation. This
point supports priority array.
1
no-units
1
no-units
93
Yes
GroupAddress (A93)
Point used to set the group address
0
no-units
0
no-units
100
Yes
Group3OccCode (A100)
Group 3 command used to put VAV
box in multiple modes of operation.
This point supports priority array.
1
no-units
1
no-units
103
No
Fusion_ZoneTemp (A103) with Actuator
The space temperature as detected
by the FusionAir sensor. (FA Variants
only)
0
°F
0
°C
105
No
ZeroOffsetCalc
Measured offset after air flow sensor
has been zeroed
0
no-units
0
no-units
106
No
Fusion_ZoneHumidity(A106) with
Actuator
The space humidity as detected by
the FusionAir sensor. (FA Variants
only)
0
%rh
0
%rh
109
No
Fusion_CO2 (A109) with Actuator
The space CO2 as detected by the
FusionAir sensor. (FA Variants only)
0
ppm
0
ppm
112
Yes
ElecHeatCFMTestTime (A112)
Amount of seconds current Flowrate
needs to be above calculated
Flowrate setpoint before enabling
electric heat. Only applicable for VAV
boxes configured for no fan or series
fan
60
sec
60
sec
113
No
Fusion_CO2 (A113) without Actuator
The space CO
₂
as detected by the
FusionAir sensor. (FA Variants only)
0
ppm
0
ppm
120
Yes
UI03_10KSensorCal (A120)
UI03 sensor calibration offset
0
°F
0
°c
122
No
UI03_10KSensorHost (A122)
Current UI03 sensor reading with
calibration offset
0
°F
0
°C
125
No
TABPriAirMaxHtgStpt
Maximum heating CFM Setpoint
0
CFM
0
l/sec
140
No
TABPriAirEffMaxStpt (A140)
Current effective maximum Flowrate
setpoint
0
CFM
0
l/sec
141
Yes
heatStateOnStpt (A141)
Temperature setpoint for setting
Primary Air State to hot when VAV
box has been configured for local
auto change over.
80
°F
27
°c
143
Yes
AO14RemoteCmd (A143)
AO14 remote command
0
%
0
%
153
Yes
TabPriAirMinHtgStpt (A153)
Primary air max heating Flowrate
setpoint. This point supports priority
array.
50
CFM
25
l/sec
154
Yes
TabFanHtgMinStpt (A154)
Minimum heating variable speed fan
command setpoint
0
%
0
%
155
No
AO14DisplayPos (A155)
AO14 display value 0
…
100%
0
%
0
%
157
Yes
CustomClosedVX10_AO15 (A157)
AO15 Close Value Custom = Volts X 10
0
%
0
%
168
Yes
Remote_SlaveTemp (A168)
Remote control temperature written
to from master controller
55
°F
21
°c
172
No
TotalHeatingStagesDefined (A172)
Amount of stages of heat defined
0
no-units
0
no-units