CBV-2U4-3T(-N) Control Sequences
CBV-2U4-3T(-N) CONTROL SEQUENCES
This section provides details of the typical control sequences used for most VAV applications. The sequences
covered in this manual include the following:
•
•
VAV Cooling only Single Speed Fan
•
VAV Cooling only Variable Speed Fan
•
VAV One to Three Stage Electric Reheat No Fan
•
VAV One to Two Stage Electric Reheat Single Speed Fan
•
VAV One to Three Stage Electric Reheat Variable Speed Fan
•
VAV Modulating Hot Water Reheat No Fan
•
VAV Modulating Hot Water Reheat Single Speed Fan
•
VAV Modulating Hot Water Reheat Variable Speed Fan
VAV COOLING ONLY NO FAN
TEMPERATURE CONTROL
When the zone temperature is greater than, or equal to, the cooling temperature setpoint, the controller will
enter the cooling mode. The primary air flow rate will be varied between its
, or
deadband setpoint, and its maximum Flowrate setpoint
the zone at the cooling temperature setpoint.
When the zone temperature falls to the heating setpoint, the controller will enter the heating mode and the
primary air flow rate will be varied between its
, or maximum heating Flowrate setpoint. Normally on a cooling-only
VAV
box both the
will be the same to maintain a minimum
rate of flow into the space while in the heating mode.
INPUT / OUTPUT POINTS
VAV Cooling Only, no fan
IO POINTS
DESCRIPTION
UI-01
Zone Temperature (with optional override button)
UI-02
Setpoint Adjustment (optional 5K slider)
UI-03
Discharge Temperature (optional)
UI-04
CO
2
, Humidity, or occupancy signal (all optional)
UI-08
Flowrate Sensor
DO-09
Damper Control (
CBV-2U4-3T-N
only)
DO-10
Damper Control (
CBV-2U4-3T-N
only)
DO-11
DO-12
DO-13
AO-14
AO-15
AO-16
Damper Control
(
CBV-2U4-3T
only)