CBV-2U4-3T(-N) Control Sequences
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
37
M
AN0
13
9
re
v
14
VAV MODULATING HOT WATER REHEAT NO FAN
TEMPERATURE CONTROL
When the zone temperature is greater than, or equal to, the cooling temperature setpoint, the controller will
enter the cooling mode. The primary air flow rate will be varied between its
deadband setpoint, and its maximum Flowrate setpoint
(A211) as required to maintain
the zone at the cooling temperature setpoint.
When the zone temperature falls to the heating setpoint, the controller will enter the heating mode and the
primary air flow rate will be varied between its
(A212), or maximum heating Flowrate setpoint. The modulating hot water reheat valve will then drive open
to maintain the desired heating setpoint.
Typically, the modulating heating valve may be controlled by either
AO-14
or
DO-11
and
D0-12
in a tri-state control
mode where
DO-11
drives the hot water valve open and
DO-12
drives it closed. There are additional options
available such as having
AO-14
as first stage modulating heat and
AO-15
as second stage modulating heat.
Input / Output Points
VAV Modulating HW Reheat, no fan AO (0
…
10 Vdc)
IO POINTS
DESCRIPTION
UI-01
Zone Temperature (with optional override button)
UI-02
Setpoint Adjustment (optional 5K slider)
UI-03
Discharge Temperature (optional)
UI-04
CO
2
, Humidity, or occupancy signal (all optional)
UI-08
Flowrate Sensor
DO-09
Damper Control (CBV-2U4-3T-N only)
DO-10
Damper Control (CBV-2U4-3T-N only)
DO-11
Tri-State Heat Valve Open
DO-12
Tri-State Heat Valve Closed
DO-13
AO-14
Modulating Heat Control (0
…
10 Vdc)
AO-15
AO-16
Damper Control (CBV-2U4-3T only)
VAV Modulating HW Reheat, no fan Tri-state
IO POINTS
DESCRIPTION
UI-01
Zone Temperature (with optional override button)
UI-02
Setpoint Adjustment (optional 5K slider)
UI-03
Discharge Temperature (optional)
UI-04
CO
2
, Humidity, or occupancy signal (all optional)
UI-08
Flowrate Sensor
DO-09
Damper Control (CBV-2U4-3T-N only)
DO-10
Damper Control (CBV-2U4-3T-N only)
DO-11
Heat Valve Open
DO-12
Heat Valve Close
DO-13
AO-14
AO-15
AO-16
Damper Control (CBV-2U4-3T only)