CBV-2U4-3T(-N) Control Sequences
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
34
M
AN0
13
9
re
v
14
VAV ONE TO THREE STAGE ELECTRIC REHEAT NO FAN
TEMPERATURE CONTROL
When the zone temperature is greater than, or equal to, the cooling temperature setpoint, the controller will
enter the cooling mode. The primary air flow rate will be varied between its
deadband setpoint, and its maximum Flowrate setpoint
(A211) as required to maintain
the zone at the cooling temperature setpoint.
When the zone temperature falls to the heating setpoint, the controller will enter the heating mode and the
primary air flow rate will be varied between its
(A212), or maximum heating Flowrate setpoint. The stages of electric heat are then staged and optionally
duty-cycled (PWM) as required to maintain the zone at the heating temperature setpoint.
INPUT / OUTPUT POINTS
VAV Electric Reheat, no fan
IO POINTS
DESCRIPTION
UI-01
Zone Temperature (with optional override button)
UI-02
Setpoint Adjustment (optional 5K slider)
UI-03
Discharge Temperature (optional)
UI-04
CO
2
, Humidity, or occupancy signal (all optional)
UI-08
Flowrate Sensor
DO-09
Damper Control (CBV-2U4-3T-N only)
DO-10
Damper Control (CBV-2U4-3T-N only)
DO-11
Electric Heat1
DO-12
Electric Heat2 (optional)
DO-13
Electric Heat3 (optional)
AO-14
AO-15
AO-16
Damper Control
(
CBV-2U4-3T
only)