CBV-2U4-3T(-N) |
Appendix : List of CBV-2U4-3T(-N) points
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
68
M
AN0
13
9
re
v
14
BINARY VALUES
POINT SETPOINT
BLOCK
OBJECTNAME
DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
DEFAULT VALUES
IMP STG.
MET
STG.
10
No
CommunicationsStatus (D10)
Communications with master controller
failure if
is enabled
On
Off
0
0
12
No
LocalDehumidControl (D12)
Enabled if local dehumidification
control has been configured
Enable
Disable
0
0
20
No
AirflowOKforElecHeat (D20)
Enabled when airflow has proved for
electric heat. Applies to VAVs with no
fan or series fan
On
Off
0
0
23
Yes
DisableLocalSetptSliderViaEMS
(D23)
Disables the local setpoint slider
On
Off
0
0
57
No
TerminalFanDefined (D57)
Enabled when controller has been
configured for a series or parallel fan
Enable
Disable
0
0
58
No
LocalCO2Control (D58)
Enabled if local CO
2
control has been
configured
Enable
Disable
0
0
65
No
LocalStptSlider (D65)
Enabled if local slide adjust has been
configured and is not disabled by point
DisableLocalSetptSliderViaEMS (D23)
Enable
Disable
0
0
78
No
FanCmdAnimation (D78)
Current fan command
On
Off
0
0
97
No
CO2ControlRemote_Slave
(D97)
CO
2
control source
Enable
Disable
0
0
100
No
Damper
Offline (D100)
Indicates bad communication for
internal damper MPBus (CBV-2U4-3T
only)
On
Off
0
0
122
No
PriAirModeEffCmd (D122)
Current Primary Air Mode Command
Enable
Disable
0
0
123
No
PriAirStateEffCmd (D123)
Current Primary Air State Command
Heatin
g
Cooling
0
0
125
No
FireStopEffCmd (D125)
Primary Air Mode Fire Stop Command
Enable
Disable
0
0
127
No
DehumidControlRemote_Slave
(D127)
Dehumidification Control Source
ON=Remote, OFF=Local
Enable
Disable
0
0
128
No
DamperStuck
CBV-2U4-3T ONLY
If after stuck damper delay (A20)
seconds the actual damper % is not
/- of stuck damper deadband
(A19) this value is true, otherwise it is
false.
On
Off
0
0
131
No
DampMaxManEff (D131)
Damper set to Max Flowrate Manual
Mode
On
Off
0
0
132
No
DampMinManEff (D132)
Damper set to Min Flowrate Manual
Mode
On
Off
0
0
133
No
DampAuxManEff (D133)
Damper set to Heat Flowrate Manual
Mode
On
Off
0
0
136
No
DampOpenManEff (D136)
Damper set Full Open Manual Mode
On
Off
0
0
137
No
DampCloseManEff (D137)
Damper set Full Close Manual Mode
On
Off
0
0
150
Yes
TABPriAirZero (D150)
TAB Calibrate Zero Airflow
On
Off
0
0
160
Yes
CmdPriAirMode (D160)
Primary Air Mode Command
Enable
Disable
0
0
161
Yes
CmdPriAirState (D161)
Primary Air State Command
Heatin
g
Cooling
0
0
163
Yes
DampAuxMan (D163)
Damper Command to Heat Flowrate
Manual Mode
On
Off
0
0
166
No
UI01DigitalStatusHost
(D166)
UI01 Digital Control value
On
Off
0
0
169
No
LocalTempSensorFault
(D169)
If zone temperature has short or open
circuit, this point will be triggered
Alarm
Normal
0
0
170
Yes
DO11RemoteCmd (D170)
DO11 override on command
On
Off
0
0
171
Yes
DO12RemoteCmd (D171)
DO12 override on command
On
Off
0
0
172
Yes
FanCoolMaxMan (D172)
Fan Commanded to Max Cool Speed
Manual Mode
On
Off
0
0
173
Yes
FanDeadbandMan (D173)
Fan Commanded to Min Speed Manual
Mode
On
Off
0
0