Maintenance 109
Location of door safety switch
The safety switch is tied into the door interlocking circuit of the drive and the interlocks
from the main circuit breaker of the drive. The interlocking system ensures that:
•
the main power can only be connected to the drive if the door is securely closed and
the safety switch is in the
locked
position.
•
the door can only be opened if the main circuit breaker is open and the DC link is
discharged.
Also, the door of the INU compartment can not be opened
•
if the drive is disconnected from the auxiliary power
•
if the safety switch of the door is in the
locked
position.
If the auxiliary voltage is switched off and the door is locked but cannot be opened, check
the position of the release dial of the safety switch. If the release dial is in the locked
position, unlock the safety switch as described in
on page
. ABB
can also provide thicker air cassette as optional for high level protection.
Safety-switch settings
There’re two kinds of safety switches as follows,
Safety-switch setting 1
Содержание ACS580MV
Страница 1: ...ABB industrial drives Hardware manual ACS580MV drives 200 kW to 6300 kW 6 kV to 11 kV...
Страница 4: ......
Страница 10: ...10...
Страница 50: ...50 Control system and interfaces...
Страница 52: ...52 Guidelines for planning the electrical installation...
Страница 77: ...Electrical installation 77 Power cable entry from top 1 screen extensions to ground 1...
Страница 90: ...90 Installation checklist...
Страница 125: ...Maintenance 125 5 Disconnect the fiber optic links from the power module 1 Hoist 2 screw M8X20 1 2...
Страница 127: ...Maintenance 127 stops it again 10 Connect the second lifting belts to the lifting eyes provided on the power module...
Страница 142: ...142 Maintenance...
Страница 144: ......
Страница 146: ...Contact us 2UBB004520 Rev E EN 2019 06 27 www abb com drives www abb com drivespartners...