78 Electrical installation
Power cable entry from bottom ((1) screen extensions to ground)
Checking the cable insulation
•
Check the insulation of each cable before connection and verify that the results are
within the specification of the cable manufacturer.
•
Leave the cables unconnected at both ends until the commissioning personnel has
given permission to connect them.
Connections
Connect the cables to their corresponding busbars:
•
Feeder cables to busbars U1, V1, W1
•
Motor cables to busbars U2, V2, W2
•
Screen ends of all conductors and the shields of all cables to the PE ground busbar
•
Ground cable to the PE ground busbar
Bolted connections
Material requirements
•
Use stainless steel bolts and nuts with the appropriate steel grade and property class
for the connection (recommended: A2-70 [designation according to ISO 3506]).
1
Содержание ACS580MV
Страница 1: ...ABB industrial drives Hardware manual ACS580MV drives 200 kW to 6300 kW 6 kV to 11 kV...
Страница 4: ......
Страница 10: ...10...
Страница 50: ...50 Control system and interfaces...
Страница 52: ...52 Guidelines for planning the electrical installation...
Страница 77: ...Electrical installation 77 Power cable entry from top 1 screen extensions to ground 1...
Страница 90: ...90 Installation checklist...
Страница 125: ...Maintenance 125 5 Disconnect the fiber optic links from the power module 1 Hoist 2 screw M8X20 1 2...
Страница 127: ...Maintenance 127 stops it again 10 Connect the second lifting belts to the lifting eyes provided on the power module...
Страница 142: ...142 Maintenance...
Страница 144: ......
Страница 146: ...Contact us 2UBB004520 Rev E EN 2019 06 27 www abb com drives www abb com drivespartners...