Program features 135
Diagnostics
Signal supervision
Six signals can be selected to be supervised by this function. Whenever a supervised
signal exceeds or falls below predefined limits, a bit in
is
activated, and a warning or fault generated.
The supervised signal is low-pass filtered.
Settings
(page
Energy saving calculators
This feature consists of the following functionalities:
• An energy optimizer that adjusts the motor flux in such a way that the total system
efficiency is maximized
• A counter that monitors used and saved energy by the motor and displays them in
kWh, currency or volume of CO
2
emissions, and
• A load analyzer showing the load profile of the drive (see separate section on
page
).
In addition, there are counters that show energy consumption in kWh of the current
and previous hour as well as the current and previous day.
Note:
The accuracy of the energy savings calculation is directly dependent on the
accuracy of the reference motor power given in parameter
.
Settings
•
Menu - Energy efficiency
(page
).
• Parameters
and
on page
Load analyzer
Peak value logger
The user can select a signal to be monitored by a peak value logger. The logger
records the peak value of the signal along with the time the peak occurred, as well as
motor current, DC voltage and motor speed at the time of the peak. The peak value is
sampled at 2 ms intervals.
Amplitude loggers
The control program has two amplitude loggers.
ACS580 FW.book Page 135 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...