Parameters 297
Actual power that the motor absorbs when connected direct-
on-line and operating the application. The value is used for
reference when energy savings are calculated.
Note:
The accuracy of the energy savings calculation is
directly dependent on the accuracy of this value. If nothing is
entered here, then the nominal motor power is used by the
calculation, but that may inflate the energy savings reported
as many motors do not absorb nameplate power.
0.00 kW
0.00…10000000.00
kW
Motor power.
1 = 1 kW
Resets the savings counter parameters
…
Done
Reset not requested (normal operation), or reset complete.
0
Reset
Reset the savings counter parameters. The value reverts
automatically to
.
1
46
46 Monitoring/scaling
settings
Speed supervision settings; actual signal filtering; general
scaling settings.
Defines the maximum speed value used to define the
acceleration ramp rate and the initial speed value used to
define the deceleration ramp rate (see parameter group
). The speed acceleration and
deceleration ramp times are therefore related to this value
(
not
to parameter
).
Also defines the 16-bit scaling of speed-related parameters.
The value of this parameter corresponds to 20000 in eg.
fieldbus communication.
1500.00 rpm;
1800.00 rpm
(
b0)
0.10…30000.00
rpm
Acceleration/deceleration terminal/initial speed.
1 = 1 rpm
Defines the maximum frequency value used to define the
acceleration ramp rate and the initial frequency value used to
define deceleration ramp rate (see parameter group
). The frequency acceleration and
deceleration ramp times are therefore related to this value
(
not
to parameter
Also defines the 16-bit scaling of frequency-related
parameters. The value of this parameter corresponds to
20000 in eg. fieldbus communication.
50.00 Hz;
60.00 Hz
(
b0)
0.10…1000.00 Hz
Acceleration/deceleration terminal/initial frequency.
10 = 1 Hz
Defines the 16-bit scaling of torque parameters. The value of
this parameter (in percent of nominal motor torque)
corresponds to 10000 in eg. fieldbus communication.
100.0%
0.1…1000.0%
Torque corresponding to 10000 on fieldbus.
10 = 1%
Defines the output power value that corresponds to 10000 in
eg. fieldbus communication. The unit is selected by
parameter
1000.00 kW
or hp
0.10 …30000.00
kW or
0.10 …40200.00 hp
Power corresponding to 10000 on fieldbus.
1 = 1 unit
Defines the 16-bit scaling of current parameters. The value of
this parameter corresponds to 10000 in fieldbus
communication.
10000 A
0…30000 A
No.
Name/Value
Description
Def/FbEq16
ACS580 FW.book Page 297 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...