238 Parameters
Defines the minimum allowed frequency.
WARNING!
This value must not be higher than
WARNING!
in frequency control mode only.
-50.00 Hz
-500.00…500.00
Hz
Minimum frequency.
See par.
Defines the maximum allowed frequency.
Note:
This parameter does not affect the frequency
acceleration and deceleration ramp times. See parameter
WARNING!
This value must not be lower than
.
WARNING!
in frequency control mode only.
50.00 Hz
-500.00…500.00
Hz
Maximum frequency.
See par.
Defines the maximum allowed motor current.
0.00 A
0.00…30000.00 A
Maximum motor current.
1 = 1 A
No.
Name/Value
Description
Def/FbEq16
ACS580 FW.book Page 238 Wednesday, September 21, 2016 9:48 PM