218 Parameters
Defines the proportional gain (K
p
) of the speed controller. Too
high a gain may cause speed oscillation. The figure below
shows the speed controller output after an error step when
the error remains constant.
10.00
If gain is set to 1, a 10% change in error value (reference -
actual value) causes the speed controller output to change by
10%, ie. the output value is input × gain.
0.00…250.00
Proportional gain for speed controller.
100 = 1
No.
Name/Value
Description
Def/FbEq16
Gain = K
p
= 1
T
I
= Integration time = 0
T
D
= Derivation time = 0
%
Controller
output = K
p
× e
Time
e = Error value
Controller output
Error value
ACS580 FW.book Page 218 Wednesday, September 21, 2016 9:48 PM