110 Program features
Motor control
Motor types
The drive supports asynchronous AC induction, permanent magnet (PM) and
synchronous reluctance motors (SynRM). Synchronous reluctance motors are,
however, supported in firmware versions ASCD2 and ASCD4 only. Only the
supported selections are shown. To check the firmware version, select
Menu -
System info - Drive
.
Motor identification
The performance of vector control is based on an accurate motor model determined
during the motor start-up.
A motor Identification magnetization is automatically performed the first time the start
command is given. During this first start-up, the motor is magnetized at zero speed
for several seconds and the motor and motor cable resistance are measured to allow
the motor model to be created. This identification method is suitable for most
applications.
In demanding applications a separate Identification run (ID run) can be performed.
Settings
(page
Scalar motor control
Scalar motor control is the default motor control method. In scalar control mode, the
drive is controlled with a frequency reference. However, the excellent performance of
vector control is not achieved in scalar control.
It is recommended to activate scalar motor control mode in the following situations:
• If the exact nominal motor values are not available or the drive needs to run
different motor after the commissioning phase
• If a short commissioning time is needed or no ID run is wanted
• In multimotor systems: 1) if the load is not equally shared between the motors, 2)
if the motors are of different sizes, or 3) if the motors are going to be changed
after motor identification (ID run)
• If the nominal current of the motor is less than 1/6 of the nominal output current of
the drive
• If the drive is used without a motor connected (for example, for test purposes)
• If the drive runs a medium-voltage motor through a step-up transformer.
• If the drive is equipped with a sine filter.
In scalar control, some standard features are not available.
ACS580 FW.book Page 110 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...