Parameters 317
0.00 PID
customer
units
.
0.00
.
32767.00
1.00
.
60.0 s
0.000 s
0.0 s
-32768.0
32767.0
.
The control program compares the absolute value of
parameter
to the deadband range
defined by this parameter. If the absolute value is within the
deadband range for the time period defined by parameter
, PID's deadband mode is activated
bit 9
is set. Then
PID's output is frozen and
is set.
If the absolute value is equal or greater than the deadband
range, PID's deadband mode is deactivated.
0.0
0.0…32767.0
Range
1 = 1
Defines the deadband delay for the deadband function. See
parameter
0.0 s
0.0…3600.0 s
Delay
1 = 1 s
.
No.
Name/Value
Description
Def/FbEq16
ACS580 FW.book Page 317 Wednesday, September 21, 2016 9:48 PM