Control macros 61
Terminal sizes:
R0…R5: 0.2…2.5 mm
2
(ter24V, DGND, DCOM, B+, A-)
0.14…1.5 mm
2
(terminals DI, AI, AO, AGND, RO, STO)
R6…R9: 0.14…2.5 mm
2
(all terminals)
Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft)
Notes:
1)
See
Menu - Primary settings - Start, stop, reference - Constant frequencies
or parameter
group
.
2)
See
Menu - Primary settings - Ramps
3)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the
grounding shelf for the control cables.
4)
Connected with jumpers at the factory.
5)
Only frames R6…R11 have terminals 40 and 41 for external 24 V AC/DC input.
6)
All control boards do not have switches S1, S2 and S3. In that case, select voltage or current
for inputs AI1 and AI2 and output AO1 with parameters
,
and
, respectively.
Input signals
•
Analog frequency reference (AI1)
•
Start/stop selection (DI1)
•
Direction selection (DI2)
•
Constant frequency selection (DI3, DI4)
•
Ramp set (1 of 2) selection (DI5)
Output signals
•
Analog output AO1: Output frequency
•
Analog output AO2: Motor current
•
Relay output 1: Ready run
•
Relay output 2: Running
•
Relay output 3: Fault (-1)
DI3
DI4
Operation/Parameter
0
0
Set frequency through AI1
1
0
0
1
1
1
DI5 Ramp set
Parameters
0
1
1
2
ACS580 FW.book Page 61 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...